ambient temperature and the settled sensitivity threshold. A self-adjustment program is switched on after 
entering  these  data  into  the  detector  memory.  The  self-adjustment  process  terminates  after  achieving  a 
reference  value  with 

  5  %  tolerance.  Afterwards,  the  decision  criteria  are  drawn  up  for  various  fire 

phenomena  runs,  for  instance  for  fast  or  slow  fire  development.  The  data  are  kept  in  the  detector  non-
volatile  memory  and  periodically  checked.  Any  measured  value  change  (against  the  assumed  decision 
thresholds) caused by a smoke, after triple verification, is treated by the microprocessor as a fire.    

 
  

4  DESIGN 

The DOP-6001 detector design is shown on Fig. 1 and Fig. 3. The detector casing, made of plastic, embraces 
electronic  circuits  and  optical  elements  of  a  transmitter  and  a  receiver  as  well  as  a  laser  diode  that 
facilitates  the  detector easy  optical  alignment.  The  lenses  for  infrared  beam  focusing  are  covered  with  a 
detachable filter. On the detector back side a connecting block is mounted, to connect power supply wires. 
The detector is fastened to the wall with a metal adjustment basis. On the detector front part, illuminating 
diodes are placed as well as the START push button that initiates the detector adjustment process.

 

The illuminating diode colour signals accordingly: 

green  one 

  a  state  of  the  detector  self-adjustment  to  the  detector-reflector/reflector  panel 

distance, when the signal level is too high; 

yellow  one 

  a  state  of  the  detector  self-adjustment  to  the  detector-reflector/reflector  panel 

distance, when signal level is too low; 

red one 

 an alarm mode; 

no light 

 a supervision mode after proper adjustment of the detector with the reflector/reflector 

panel.  

The  START  push  button  enables  initiation  of  the  detector  adjustment  process  (self-adjustment)  and  the 
detector parameters renewed set-up after optical parts cleaning works.   

 

5  INSTALLATION 

The DOP-6001 detector interoperates with a reflector panel and then its operating distance ranges from 50 
m  to  100  m,  or  with  an  E39-R8  prism  reflector  at  the  operating  distance  between  5  m  and  50  m.  It  is 
possible to install up to 64 DOP-6001 detectors in one POLON 4000 system addressable line. 

The  reflector  or  the  reflector  panel  as  well  as  the  M42-00  00  00  service  kit,  containing  test  foils  and  an 
adjustment mirror, are not included in the detector standard pack and should be ordered separately. 

Up to 64 DOP-6001 detectors can be installed in one addressable detection line of the POLON 4000 system. 
Only one DOP-6001 detector without end-of-line resistors can be installed in one conventional line. 

In case the detector is seen with difficulty or is installed in a hardly accessible place, it is possible to connect 
the WZ-31 additional operation indicator to be placed in a convenient and visible place.  

Before installation, it is necessary to declare an alarm mode and a sensitivity threshold. The operations are 
executed using appropriate jumpers placed on the back side of the detector casing, pursuant to Fig. 6. One 
of  the  criteria  taken  into  consideration  when  choosing  sensitivity  may  be  the  distance  between  the 
detector and the reflector/reflector panel, and so: 

-

 

for a distance from 5 m to 20 m 

 18 % sensitivity is recommended; 

-

 

for a distance from 20 m to 50 m 

 30 % sensitivity is recommended; 

-

 

for a distance from 50 m to 100 m 

 50 % sensitivity is recommended. 

It is possible to set sensitivity level experimentally: adopting it to a certain environment in the case of the 
detector  difficult  operating  conditions.  The  DOP-6001  detector  and  the  reflector/reflector  panel  are 

Summary of Contents for POLON 4000 DOP-6001

Page 1: ...IK E343 001E 1 POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DOP 6001 OPTICAL BEAM SMOKE DETECTOR Installation and maintenance manual IK E343 001E Edition I ...

Page 2: ...łka z ograniczoną odpowiedzialnością Sp k Glinki 155 Street PL 85 861 Bydgoszcz 11 1438 CPD 0219 PN EN 54 12 DOP 6001 Beam smoke detector operates using absorbed light beam addressable conventional undetachable Application fire security Technical data IK E343 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in t...

Page 3: ...s alignment between the detector and the reflector reflector panel The DOP 6001 beam smoke detector is intended for installation in the POLON 4000 system fire detection and alarm control panel lines The detector operates in closed premises at ambient temperatures ranging from 25 o C to 55 o C and relative humidity up to 95 at 40 o C 2 TECHNICAL SPECIFICATIONS Operating voltage in a detection line ...

Page 4: ... to monitor its contamination and environ impact conditions The circuits ensure the same sensitivity threshold in the whole compensation range At a certain contamination level the detector signals a fault mode denoting a necessity to undertake servicing and cleaning works However even in this mode the detector is still able to detect smoke and initiate an alarm A contamination caused fault require...

Page 5: ...reflector panel The START push button enables initiation of the detector adjustment process self adjustment and the detector parameters renewed set up after optical parts cleaning works 5 INSTALLATION The DOP 6001 detector interoperates with a reflector panel and then its operating distance ranges from 50 m to 100 m or with an E39 R8 prism reflector at the operating distance between 5 m and 50 m I...

Page 6: ...lector The mirror should be removed after proper regulation of the optical path between the detector and the reflector The prism reflector position cannot be adjusted and it is recommended to fix it to a flat substrate with screws or glue The detector is properly aligned with the reflector reflector panel when the reflected laser light illuminates the detector In such the situation the external ba...

Page 7: ... detector testing foil with overprints is included in the service kit During renovation or painting works carried out in the premises where detectors are installed the detector and reflector reflector panel should be taken out Detectors which are damaged in the time of painting and renovation works due to a fault of persons who execute them are not subject to warranty repairs 7 SAFETY CONDITIONS 7...

Page 8: ...7 m 0 4 m to 1 0 m Over 12 m 7 m 0 6 m to 0 9 m 0 8 m to 1 2 m The maximum area protected by one detector in case the detector reflector panel distance is 100 m for the ceiling height at 10 m amounts to 2D x 100 m ca 1300 m2 so the detector can replace a dozen of spot smoke detectors The distance between the detector IR beam and a side wall of room should not exceed D value and between two adjacen...

Page 9: ...1E 9 Fig 3 DOP 6001 design and overall dimensions Note Only one detector without an end of line resistor can be installed in a conventional detection line therefore no line output to the next detector is provided ...

Page 10: ...10 IK E343 001E Fig 4 DOP 6001 detector installation wires connection Fig 5 DOP 6001 detector internal connections and output terminals diagram ...

Page 11: ... declared in the control panel and all jumpers should be taken out Interoperating line declaration no jumper POLON 4000 system addressable line jumper in ADC1 position TELSAP side line behind ADC1 adapter jumpers in ADC38 and ADC1 position ALFA 3800 side line behind ADC1 adapter jumpers in ADC38 and ADC1 position IGNIS 1000 or CSP 35 system conventional line Fig 6 Jumpers for detector operation de...

Page 12: ...12 IK E343 001E Fig 8 Reflector panel ...

Page 13: ...IK E343 001E 13 Fig 9 DOP 6001 detector testing foil with overprints ...

Page 14: ...14 IK E343 001E Fig 10 Reflector panel assembly IK E343 001E 03 2012 04 2012 ...