background image

14 

IK-E343-001E 

 

 

 

 
 
 

 

 

 

Fig. 10. Reflector panel assembly 

 
 
 
 
 
 
 
 
IK-E343-001E/03.2012/04.2012 

Summary of Contents for POLON 4000 DOP-6001

Page 1: ...IK E343 001E 1 POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DOP 6001 OPTICAL BEAM SMOKE DETECTOR Installation and maintenance manual IK E343 001E Edition I ...

Page 2: ...łka z ograniczoną odpowiedzialnością Sp k Glinki 155 Street PL 85 861 Bydgoszcz 11 1438 CPD 0219 PN EN 54 12 DOP 6001 Beam smoke detector operates using absorbed light beam addressable conventional undetachable Application fire security Technical data IK E343 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in t...

Page 3: ...s alignment between the detector and the reflector reflector panel The DOP 6001 beam smoke detector is intended for installation in the POLON 4000 system fire detection and alarm control panel lines The detector operates in closed premises at ambient temperatures ranging from 25 o C to 55 o C and relative humidity up to 95 at 40 o C 2 TECHNICAL SPECIFICATIONS Operating voltage in a detection line ...

Page 4: ... to monitor its contamination and environ impact conditions The circuits ensure the same sensitivity threshold in the whole compensation range At a certain contamination level the detector signals a fault mode denoting a necessity to undertake servicing and cleaning works However even in this mode the detector is still able to detect smoke and initiate an alarm A contamination caused fault require...

Page 5: ...reflector panel The START push button enables initiation of the detector adjustment process self adjustment and the detector parameters renewed set up after optical parts cleaning works 5 INSTALLATION The DOP 6001 detector interoperates with a reflector panel and then its operating distance ranges from 50 m to 100 m or with an E39 R8 prism reflector at the operating distance between 5 m and 50 m I...

Page 6: ...lector The mirror should be removed after proper regulation of the optical path between the detector and the reflector The prism reflector position cannot be adjusted and it is recommended to fix it to a flat substrate with screws or glue The detector is properly aligned with the reflector reflector panel when the reflected laser light illuminates the detector In such the situation the external ba...

Page 7: ... detector testing foil with overprints is included in the service kit During renovation or painting works carried out in the premises where detectors are installed the detector and reflector reflector panel should be taken out Detectors which are damaged in the time of painting and renovation works due to a fault of persons who execute them are not subject to warranty repairs 7 SAFETY CONDITIONS 7...

Page 8: ...7 m 0 4 m to 1 0 m Over 12 m 7 m 0 6 m to 0 9 m 0 8 m to 1 2 m The maximum area protected by one detector in case the detector reflector panel distance is 100 m for the ceiling height at 10 m amounts to 2D x 100 m ca 1300 m2 so the detector can replace a dozen of spot smoke detectors The distance between the detector IR beam and a side wall of room should not exceed D value and between two adjacen...

Page 9: ...1E 9 Fig 3 DOP 6001 design and overall dimensions Note Only one detector without an end of line resistor can be installed in a conventional detection line therefore no line output to the next detector is provided ...

Page 10: ...10 IK E343 001E Fig 4 DOP 6001 detector installation wires connection Fig 5 DOP 6001 detector internal connections and output terminals diagram ...

Page 11: ... declared in the control panel and all jumpers should be taken out Interoperating line declaration no jumper POLON 4000 system addressable line jumper in ADC1 position TELSAP side line behind ADC1 adapter jumpers in ADC38 and ADC1 position ALFA 3800 side line behind ADC1 adapter jumpers in ADC38 and ADC1 position IGNIS 1000 or CSP 35 system conventional line Fig 6 Jumpers for detector operation de...

Page 12: ...12 IK E343 001E Fig 8 Reflector panel ...

Page 13: ...IK E343 001E 13 Fig 9 DOP 6001 detector testing foil with overprints ...

Page 14: ...14 IK E343 001E Fig 10 Reflector panel assembly IK E343 001E 03 2012 04 2012 ...