background image

IK-E286-001E 

with Fig. 5. Any input lines closing or opening is detected by the monitoring and controlling element 
and signalled by the control panel as an input line default. The EKS-4001 monitoring and controlling 
element proper connection is shown in Fig. 5.  
 

 

6  

INSTALLATION 

The monitoring and controlling elements are recommended to be installed in the controlled devices 
vicinity.  The  monitoring  and  controlling  elements  cases  should  me  mounted  on  walls  and  ceilings 
fastening  four  screws  through  the  openings  in  the  corners.  It  is  advised  to  take  the  modules  out 

when the case is mounted and use screws with Ø6 expansion anchor bol

ts. 

The installation wires should be introduced through cable gland seals. The detection line conductors 

 1 x 2 x 0.8 wire is recommended 

 should be introduced through two smaller PG7 cable gland seals, 

whereas monitoring and controlling conductors - 3 x 2 x 0.8 wire is recommended 

 should be routed 

through bigger PG9 cable gland seals. 

It is important that the cable gland seals are properly sealed and unused gland seals are plugged (all 
cable gland seals are plugged by default).  

For  installation  wires  connection  a  screw  driver  use  is  recommended,  its  operation  part  should  be 
pushed in as far as it goes (see below figure) into the connector smaller hole. Then the wire should 
be inserted into the bigger hole and the screw driver should be taken off. It is advised to use a short, 
bended WAGO type  screw driver (3.5 x 0.5 mm, cat. No. 210-258) that is available for purchase at 
POLON-ALFA). The wires connection should be done pursuantly to the descriptions on the connector. 
Wires screens should be twisted together and fasten with the screw with washer placed between the 
slots on the mounting plate. 

 

 

7  

SERVICING AND MAINTENANCE 

The  monitoring  and  controlling  element  unfailing  operation  depends  on  maintaining  appropriate 
operating  conditions,  proper  installation  and  periodic  inspections  performance.  The  periodic 
inspections should be carried out at least once per six months by a person who knows the element 
operation  to  such  an  extent  that  allows  revealing  its  malfunctions.  The  inspection  consists  in  the 
element functioning checking in an acting detection installation. 

Summary of Contents for EKS-4001

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM EKS 4001 MICROPROCESSOR BASED ADDRESSABLE MONITORING AND CONTROLLING ELEMENT Installation and Maintenance Manual IK E286 001E IIIB Edition ...

Page 2: ...polon alfa pl web site 1438 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 06 1438 CPD 0071 EN 54 18 Input output device EKS 4001 addressable monitoring and controlling element Technical data IK E286 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the man...

Page 3: ...olled device by line continuity monitoring circuit 615 µA Relay controlling output non potential switchable contact 2 A 30 V Tp relay actuation delay time 2 s 30 s 60 s 90 s Number of monitoring outputs 2 Monitoring lines capacity 65 nF ca 350 m of 1x2x0 8 mm cable Monitoring output initiation NO or NC non potential contact Tk elapsing time after which controlled device monitoring starts no monito...

Page 4: ...he module with the terminal block in the CUBO S type case The following case sizes are available for one two and four EKS 4001 modules The case bases are drilled in the corners to provide openings for wall mounting Two PG7 cable gland seals are located in the case base side wall in order to insert the detection line inputs and outputs Additionally two or four depending on the case type PG9 cable g...

Page 5: ...e control panel information about a non maskable fault The way how the monitoring and controlling element works is determined by the element operation mode During the system automatic configuration the default mode settled by the manufacturer is set i e 10000000 in the binary recording 80 in the hexadecimal recording It means that the EKS monitors the controlled device line continuity the relay ac...

Page 6: ...land seals are properly sealed and unused gland seals are plugged all cable gland seals are plugged by default For installation wires connection a screw driver use is recommended its operation part should be pushed in as far as it goes see below figure into the connector smaller hole Then the wire should be inserted into the bigger hole and the screw driver should be taken off It is advised to use...

Page 7: ...ld not be exposed to either direct sunlight or heat from heating equipment The EKS 4001 elements storage period in transportation packing should not exceed 6 months The EKS 4001 monitoring and controlling elements should be carried in closed transport means spaces in packing that meets the requirements of transportation regulations in force The temperature during transportation should not be lower...

Page 8: ...8 IK E286 001E Fig 2 1xEKS case dimensions ...

Page 9: ...IK E286 001E 9 Fig 3 2xEKS case dimensions ...

Page 10: ...10 IK E286 001E Fig 4 4xEKS case dimensions ...

Page 11: ...IK E286 001E 11 Fig 5 Exemplary diagram of EKS 4001 element in 1xEKS case connection in detection line Fig 6 EKS case connection terminals view IK E286 001 03 2009 05 2012 ...

Reviews: