!!! PLEASE NOTE
Before connecting the power supply, make sure that all detectors have the same
common contact function selected; in the case of incorrect settings, there is a risk of a
short circuit during the test, an alarm condition or a fault.
!!! PLEASE NOTE
The supply circuit and the control circuit must be protected with over-current fuses.
After connecting the power supply and heating all sensors, you can perform the installation test
according to the procedure 8.1. After the positive test result, the detector covers can be mounted,
making sure that the sensor covers are mounted and located in the correct position (applies only to
detectors ASG-2001 and ASG-2002). Lack of the sensor cover reduces the protection of the housing to
IP43, and detector operation without the sensor cover is not allowed. For ASG-2003 detectors, check
whether the sensor insulation has been damaged.
Figure 3. Scheme of installation of the 3-threshold system, control wires connected to the phase wire.
Disconnector with overcurrent fuse
A1 CONTROL
VENTILATION SYSTEM
A2 CONTROL
Use for loads below 1A
A3 CONTROL
Use for loads below 1A