Special attention shall be given to the stability of ladders, platforms, etc. 

Any  electric  tool  shall  be  used  strictly  obeying  the  safety  rules  specified  in  the  manufacturer  instruction 
manuals.  

 

3.3   Anti-dusting eye protection  

It  is  obligatory  to  use  protective  anti-dusting  glasses  and  masks  during  detector  installation  works  that 
produce high amount of dust, such as hole drilling for detector base mounting on ceilings. 
 
 

4   DESIGN DESCRIPTION 

 
The  ADC-4001M  adapter  is  placed  in  a  casing  similar  to  those  of  40 model  range  detectors,  however  the 
casing is not ribbed – the upper part is entirely closed. A cover is fitted to the casing and a two-colour diode 
is located from the front side. The adapter is mounted in the G-40 installation base, where also installation 
wires and cables screens are fixed to.  

 

 

 

Fig.1   ADC-4001M adapter 

 

 

5   OPERATION DESCRIPTION

 

 

The ADC-4001M adapter is an addressable device operating in a loop-shaped detection line that monitors 
two-stage  detectors  installed  in  its  branch  line.  All  line  elements,  installed  in  the  branch  line,  possess  a 
common address determined by the adapter. 

A fire signal induced by a detector installed in the branch line is transmitted via the adapter to the control 
panel whereas it is signalled in the adapter with a red flashing diode light. 

A branch line fault (short circuit or breakage) is also transmitted to the control panel; in this case the diode 
flashes with a yellow light. Any branch line fault does not have any impact on the detection line. 

The adapter is equipped with internal short-circuit isolator that cuts off the efficient part of the addressable 
detection loop. The isolator, after revealing a voltage decrease on its contacts, resulted from a short circuit 
in  the  detection  line,  cuts  off  the  shorted  section.  The  short-circuit  separation  is  signalled  with  a  yellow 
diode flashings and appropriate information is passed to the control panel. 

The  adapter  operates  in  six  working  modes.  A  proper  mode  shall  be  declared  at  the  control  panel.  The 
mode selection is provided in order to optimise the adapter current consumption adjusting it to particular 
needs (see Table 1).  

 

Summary of Contents for ADC-4001M

Page 1: ...1 IK E283 001E POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM ADC 4001M ADAPTER Installation and maintenance manual IK E323 001E Edition IA ...

Page 2: ...Spółka z ograniczoną odpowiedzialnością Sp k Glinki 155 Street PL 85 861 Bydgoszcz 05 1438 CPD 0069 EN 54 18 ADC 4001M adapter Addressable alarm signal input element detachable Technical data IK E323 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the manual may be harmful or may cause violation of the law i...

Page 3: ... evokes a fire alarm at the control panel The adapter is equipped with a short circuit isolator The ADC 4001M adapter is intended for wall or ceiling mounting using the G 40 base 2 TECHNICAL SPECIFICATIONS Operation voltage from detection loop 16 5 V 24 6 V Current drawn from detection loop from 0 5 mA to 16 mA depending on operation mode Maximum branch line resistance 2 x 25 Ω Operation temperatu...

Page 4: ... stage detectors installed in its branch line All line elements installed in the branch line possess a common address determined by the adapter A fire signal induced by a detector installed in the branch line is transmitted via the adapter to the control panel whereas it is signalled in the adapter with a red flashing diode light A branch line fault short circuit or breakage is also transmitted to...

Page 5: ...de intended exclusively for DOP 40 beam smoke detector connection without an end of line resistor the detector jumper set in ADC 1 position Mode 6 mode provided especially for interoperation with 40 model range detectors of low voltage power supply It enables installation of up to 5 40 model range detectors manufactured after June 15th 2002 date stated in a warranty certificate Detailed informatio...

Page 6: ...ntrinsically safe smoke detector or up to 10 pcs intrinsically safe manual call points equipped with a 1 kΩ alarm resistor system limitation NOTE A branch line short circuit behind an intrinsically safe separator is signalled as a fire alarm A line short circuit between a separator and an adapter is signalled as a fault The separator should be installed in a safe zone directly behind an endangered...

Page 7: ...hould be squeezed with fingers then the connector should be placed between the guides in the base rectangular hollow 8 SERVICING AND MAINTENANCE The ADC 4001M adapter unfailing operation depends on ensuring proper operation conditions appropriate assembly execution and systematic periodical inspection The periodical checks should be carried out at least yearly by a person who knows the device oper...

Page 8: ...8 IK E283 001E Fig 2 ADC 4001M adapter exemplary connection into addressable detection line with exemplary adapter branch line connection IK E323 001E 05 2009 01 2012 ...

Reviews: