IK-E283-001E 

Table 1 

ADC working 

mode 

Addressable loop 

current drawn by ADC 

Admissible quiescent 

current of branch line 

detectors 

Ra alarming 

resistor  

Rk branch line 

end-of-line resistor 

6.8 mA 

1.0 mA 

1 kΩ 

13 kΩ 

16 mA 

2.0 mA 

1 kΩ 

5.6 kΩ 

2.5 mA 

150 uA 

1 kΩ 

47 kΩ 

0.5 mA 

8.2 kΩ 

13 kΩ 

2.2 mA 

1.33 mA 

300 uA 

1 kΩ 

33 kΩ 

 
The entire current consumption by the adapter, regardless its state and the number of elements installed in 
the branch line, is constant for a given operation mode.  

Mode „1” -  enables installation of up to 10 two-state detectors. 

Mode „2” -  the number of detectors installed in the branch line cannot exceed 20.  

Mode „3” -  enables installation of 1 - 2 two-state detectors. 

Mode „4” -  mode  provided  for  interoperation  with  devices  (e.g.  monitoring-alarming  valves  of  sprinkling 

systems) that are equipped with non-potential NO contacts. An alarm is activated by connecting 
to the branch line through an 8.2 kΩ resistor contact. 

Mode „5” -  mode  intended  exclusively  for  DOP-40  beam  smoke  detector  connection  (without  an  end-of-

line resistor – the detector jumper set in ADC-1 position). 

Mode „6” -  mode  provided  especially  for  interoperation  with  40-model  range  detectors  of  low  voltage 

power  supply.  It  enables  installation  of  up  to 5 40-model  range  detectors manufactured  after 
June 15

th

, 2002 (date stated in a warranty certificate). 

Detailed information regarding designing rules of detection lines with ADC-4001M detectors installed in is 
contained in the POLON 4000 system control panel manuals.  

 
 

6   POLON 4000 INTRINSICALLY SAFE DETECTION LINES 

 
The  POLON  4000  intrinsically  safe  detection  lines  can  be  routed  only  as  branch  lines  behind  ADC-4001M 
adapters using intrinsically safe separators manufactured by STAHL: 

 

one-channel type   

9167/13-11-00s; 

 

two-channel type   

9167/23-11-00s. 

Maximum  adapter  branch  line  resistance  shall  not  exceed  2  x  25  Ω  (including  both  sections:  before  and 
behind the separator). 

The ADC-4001M adapter operation mode should be assorted suitably to a type and number of intrinsically 
safe detectors or manual call points installed in an intrinsically safe line (see Table 2). 

 

 

 

Summary of Contents for ADC-4001M

Page 1: ...1 IK E283 001E POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM ADC 4001M ADAPTER Installation and maintenance manual IK E323 001E Edition IA ...

Page 2: ...Spółka z ograniczoną odpowiedzialnością Sp k Glinki 155 Street PL 85 861 Bydgoszcz 05 1438 CPD 0069 EN 54 18 ADC 4001M adapter Addressable alarm signal input element detachable Technical data IK E323 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the manual may be harmful or may cause violation of the law i...

Page 3: ... evokes a fire alarm at the control panel The adapter is equipped with a short circuit isolator The ADC 4001M adapter is intended for wall or ceiling mounting using the G 40 base 2 TECHNICAL SPECIFICATIONS Operation voltage from detection loop 16 5 V 24 6 V Current drawn from detection loop from 0 5 mA to 16 mA depending on operation mode Maximum branch line resistance 2 x 25 Ω Operation temperatu...

Page 4: ... stage detectors installed in its branch line All line elements installed in the branch line possess a common address determined by the adapter A fire signal induced by a detector installed in the branch line is transmitted via the adapter to the control panel whereas it is signalled in the adapter with a red flashing diode light A branch line fault short circuit or breakage is also transmitted to...

Page 5: ...de intended exclusively for DOP 40 beam smoke detector connection without an end of line resistor the detector jumper set in ADC 1 position Mode 6 mode provided especially for interoperation with 40 model range detectors of low voltage power supply It enables installation of up to 5 40 model range detectors manufactured after June 15th 2002 date stated in a warranty certificate Detailed informatio...

Page 6: ...ntrinsically safe smoke detector or up to 10 pcs intrinsically safe manual call points equipped with a 1 kΩ alarm resistor system limitation NOTE A branch line short circuit behind an intrinsically safe separator is signalled as a fire alarm A line short circuit between a separator and an adapter is signalled as a fault The separator should be installed in a safe zone directly behind an endangered...

Page 7: ...hould be squeezed with fingers then the connector should be placed between the guides in the base rectangular hollow 8 SERVICING AND MAINTENANCE The ADC 4001M adapter unfailing operation depends on ensuring proper operation conditions appropriate assembly execution and systematic periodical inspection The periodical checks should be carried out at least yearly by a person who knows the device oper...

Page 8: ...8 IK E283 001E Fig 2 ADC 4001M adapter exemplary connection into addressable detection line with exemplary adapter branch line connection IK E323 001E 05 2009 01 2012 ...

Reviews: