Configuration level
19
KS40-1 burner
Name
Value range
Description
Default Own
setting
FAIL
Behavior at sensor break
1
0
Controller outputs switched of
1
y = Y2
2
y=meanoutput.Themaximumpermissibleoutputcanbeadjustedwith
parameter
Ym.H
.Topreventdeterminationofinadmissiblevalues,meanvalue
formationisonlyifthecontroldeviationislowerthanparameter
L.Ym
.
rnG.L
-1999...9999
X0 (low limit range of control)
1
0
rnG.H
-1999...9999
X100 (high limit range of control)
1
100
1
rnG.L
and
rnG.H
indicate the control range to which e.g. self-tuning is related.
InP.1
Name
Value range
Description
Default
Own
setting
S.tYP
Sensor type selection
50
0
Thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
Thermocouple type J (-100...1200°C) , Fe-CuNi
2
Thermocouple type K (-100...1350°C), NiCr-Ni
3
Thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
Thermocouple type S (0...1760°C), PtRh-Pt10%
5
Thermocouple type R (0...1760°C), PtRh-Pt13%
20
Pt100 (-200,0 ... 100,0 °C)
21
Pt100 (-200,0 ... 850,0 °C)
22
Pt1000 (-200,0...200,0 °C)
23
KTY 11-6 (special 0...4500 Ohm)
30
0...20mA / 4...20mA
2
40
0...10V / 2...10V
2
50
Potentiometer 0...160 Ohm
2
51
Potentiometer 0...450 Ohm
2
52
Potentiometer 0...1600 Ohm
2
S.Lin
Linearization (only at
S.tYP
= 30 (0..20mA) and 40
(0..10V) adjustable)
0
0
None
1
Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The characteristic
for KTY 11-6 temperature sensors is preset.
Corr
Measured value correction ( scaling
2
0
Without scaling
1
Offset correction (at
CAL
level)
2
2- point correction (at
CAL
level)
3
Scaling (at
PArA
level)
2
With current, voltage or potentiometer input signals, scaling is required (see section 5.1).