44
120
119
maxPres_AI
N1
Max. Air supply
pressure
–
analog
sensor
I/O
0
4000
100
integer
Unit: Pa
121
120
maxPres_AI
N2
Max. Exhaust
pressure
–
analog
sensor
I/O
0
4000
100
integer
Unit: Pa
List of BMS alarms
BMS
Index
Modbus
address
Variable
name
Description
Signal
type
Variable
type
Comments
Min.
Max.
Default
122
200
SAP_AL
SAP alarm
O
0
1
0
integer
0
–
inactive,
1 - active
123
201
Service_AL
General inspection
required
O
0
1
0
integer
0
–
inactive,
1 - active
124
202
Filter_AL
Filter replacement
required
O
0
1
0
integer
0
–
inactive,
1 - active
125
203
Filter_AL_SU
P
Air supply dirty
filter
–
pressure
switch action
O
0
1
0
integer
0
–
inactive,
1 - active
126
204
Filter_AL_EX
H
Exhaust dirty filter
–
pressure switch
action
O
0
1
0
integer
0
–
inactive,
1 - active
127
205
Sensor_T2_
AL
Sensor T2
malfunction
O
0
1
0
integer
0
–
inactive,
1 - active
128
206
Sensor_T3_
AL
Sensor T3
malfunction
O
0
1
0
integer
0
–
inactive,
1 - active
129
207
Sensor_T4_
AL
Sensor T4
malfunction
O
0
1
0
integer
0
–
inactive,
1 - active
130
208
Sensor_T5_
AL
Sensor T6
malfunction
O
0
1
0
integer
0
–
inactive,
1 - active
131
209
Sensor_T6_
AL
Sensor T5
malfunction
O
0
1
0
integer
0
–
inactive,
1 - active
132
210
Sensor_T1_
AL
Sensor T1
malfunction
O
0
1
0
integer
0
–
inactive,
1 - active
133
211
-
-
-
-
-
-
-
-
134
212
sup_HT_AL
Air supply high
temperature
O
0
1
0
integer
0
–
inactive,
1 - active
135
213
sup_LT_AL
Air supply low
temperature
O
0
1
0
integer
0
–
inactive,
1 - active
136
214
Hex_frost_A
L
Frosted exchanger
O
0
1
0
integer
0
–
inactive,
1 - active
137
215
N1_HT_temp
_AL
Possible primary
heater overheat
O
0
1
0
integer
0
–
inactive,
1 - active
138
216
N2_HT_temp
_AL
Possible secondary
heater overheat
O
0
1
0
integer
0
–
inactive,
1 - active
139
217
N1_HT_AL
Electric primary
heater overheat
O
0
1
0
integer
0
–
inactive,
1 - active
140
218
N2_HT_AL
Electric secondary
heater overheat
O
0
1
0
integer
0
–
inactive,
1 - active
141
219
Frost_AL
Activation of
soaking process
for secondary
heater
O
0
1
0
integer
0
–
inactive,
1 - active
Parameter type: O
–
only Output
–
read only parameter, I/O
–
Input/Output
–
read and
modification allowed.
Summary of Contents for ecoVENT MIDI
Page 6: ...6...
Page 7: ...7 USER MANUAL ecoVENT MIDI...
Page 20: ...20...
Page 25: ...25...
Page 26: ...26 INSTALLATION AND SERVICE SETTINGS ecoVENT MIDI...
Page 56: ...56...
Page 57: ...57 Assembly dimensions of the MIDI module...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...