13
In PAUSE mode the boiler is being burnt off
and awaits the signal to start operation. The
following can be a signal to start operation:
Decrease of preset boiler temperature
below preset temperature diminished by
boiler hysteresis (
Boiler hysteresis
),
By boiler operation configuration with the
buffer decrease of top buffer temperature
below preset value (
Buffor loading start
temperature
).
8.10
GRATE
Some boilers have an additional grate to
burn other fuels such as wood waste, etc. To
activate the grid, move the parameters
available in the:
Main menu
→
Boiler settings
→
Boiler
oper. mode
from "pellet" to "grid". In the grid mode fuel
feeder is turned off. The combustion process
is regulated by the fan. Fan power, when
working with grid, is set in:
Boiler settings
→
Output modulation
→
Blow-in output – grate
The values of parameters such as:
Boiler
settings
→
Preset
boiler
temperature
Boiler settings
→
Output modulation
→
Boiler hysteresis
Service Settings
→
Burner settings
→
Fuel detection time
are individually adjusted for the "grate". This
allows you to define different properties of
boiler operation for operation modes "grate"
and "pellets".
When using the grid an alarm "No fuel" can
appear. This alarm occurs when a
temperature drops below the value of the
parameter:
Menu
→
Service settings
→
CH and HUW
settings
→
CH activation temp.
and then
for a period of 10 minutes there has been no
growth.
8.11
HOT WATER SETTINGS
The controller regulates temperature of the
silo of Hot Water HW, providing that the
temperature sensor is connected. When the
sensor is disconnected – the information
about it is displayed in the main window. By
selecting:
Menu
→
HUW settings
→
HUW
Pump mode
the user is able to:
deactivate feeding the silo, parameter
Deactivated
,
setting HUW priority, by parameter
Priority
– then CH pump is deactivated to
feed the HUW boiler quicker,
set simultaneous operation of CH and
HUW pump with the parameter
No
priority
,
Activate function
Summer
.
8.12
HOT WATER TEMPERATURE
SETTINGS
Preset temperature HUW is defined by
parameter:
Menu
→
HUW settings
→
Preset HUW
temperature
8.13
HYSTERESIS OF HOT WATER
FEEDER
Below temperature
Preset temperature HUW
–
Silo hysteresis HUW
the HUW pump will
activate to feed the HUW silo.
By small hysteresis value HUW
pump will activate faster after HUW
temperature decrease.
8.14
SUMMER FUNCTION START UP
To activate SUMMER function which allows
feeding the silo during summer, without
necessity to activate CH installation and
mixers periods, it is required to set the:
Menu
→
Summer/Winter
→
SUMMER
mode for
Summer
.
Attention: when boiler operates
without heating buffer and the
controller is switched into SUMMER
mode,
than
Standard
mode
operation is is recommended. point
8.6
It is not allowed to activate
function summer when HW pump is
disconnected or damaged.
Function
SUMMER
can
be
activated
automatically, on the basis of readings from