3.2 Wiring the Power Inputs
The upper panel of the Industrial Serial Server indicates a DC inlet
power socket and consists of one terminal block connector within 6
contacts. Please follow the steps below to insert the power wire.
1
.
Insert positive/negative DC power wires into
Contacts 1 and 2
for
Power 1
, or
Contacts 5 and 6
for
Power 2
. Figure 3-1 and 3-2
show PWR1 and PWR2 of the Industrial Serial Server.
ICS-2200T: 12~48V DC
V1+ V1-
V2+ V2-
PWR1
PWR2
Fault
DC Input:
12-48V , 1Amax.
1 2 3 4 5 6
Figure 3-1:
ICS-2200T Upper Panel
ICS-2400T: 12~48V DC
1A@24V
V1+ V1-
V2+ V2-
PWR1
PWR2
Fault
DI1 DO0 DO1
DI0
GND
GND
DC Input:
12-48V , 1Amax.
1 2 3 4 5 6
1 2 3 4 5 6
Figure 3-2:
ICS-2400T Upper Panel