8 TECHNICAL DATA
8.1 General data
SIL level (SIL CL):
up to SIL 3 according to
EN 62061+A1:2013 / IEC 61508:2010
Performance Level (PL):
up to PL e according to EN ISO 13849-1:2008
Safety category:
up to Cat.4 according to EN ISO 13849-1:2008
MTTF
d
: 431
PFH
d
: 7.08E-09
Mission time:
20 years
Response time:
< 30 ms
Ambient temperature:
0°C ... +55°C
Storage temperature:
-20°C ... +70°C
Pollution degree:
outside 3, inside 2
Over-voltage category:
II
Rated impulse with stand voltage U
imp
:
0.8 kV
Weight:
250 g
8.2 Housing
Material:
Polyamide PA 6.6 class V0 (UL94)
Protection degree:
IP 40 (housing), IP 20 (terminal board)
Dimensions (L x H x S):
111.5 x 99.0 x 45 mm
Cross section of the conductors:
0.2 ... 2.5 mm
2
24 ... 12 AWG
Terminals driving torque:
0.5 ... 0.6 Nm
Mounting:
Din-rail 35x7.5 EN 50022
8.3 Power supply
Rated operating voltage A1-A2 U
n
:
24 Vdc
Max residual ripple in DC:
10%
Supply voltage tolerance:
- 15% ... +15% of Un
Rated power consumption (without load):
< 3 W
Internal general protection:
PTC, Ih=1.5 A
Operating time of PTC:
intervention > 100 ms, reset > 3 s
Internal protection against outputs (Tx, Ox)
short circuits:
electronic
Max outputs (Tx, Ox) currents sum:
0.5 A
Self test time at start up:
< 2 s
8.4 Inputs circuits (Ix)
Inputs number:
4
Input voltage and current:
24 V, 5 mA
Inputs signal:
0-8 V (Off), 12-24 V (On)
Galvanic insulation:
No
Min length inputs signal:
10 ms
Inputs signal filtering:
Yes, max spike length 0.4 ms
Max inputs resistance:
100
Ω
Max inputs capacity:
470 nF toward ground and between the conductors
8.5 Analogue input circuits (Cx)
Number of inputs:
2
Rated supply voltage:
24 Vdc ± 15 %
Analogue input type:
4-20 mA current loop
Measurement range:
0 … 25 mA
Accuracy over entire measurement range:
1 % ± 1 digit
Resolution:
0.01 mA
Input resistance:
100 Ohm
Maximum applicable current:
30 mA
Managed sensors:
“source” type with 2/3 wires
Galvanic separation:
Yes
Insulation voltage (Ui):
500 V
NB: Voltage and current values indicated refer to the power supply terminals (Ax, see each module individually) of the
board housing the Cx type terminals
8.6 Testing signal circuits (Tx)
Test signal number:
4
Signal type
Pulsed 100 Hz 24V-0V, duty cycle 50%
Max current per test signal:
0.2 A
Max currents sum:
see 8.3 Power supply
Protection against short circuits
Yes
Galvanic insulation:
No
8.7 Semiconductor signal output circuits (Ox)
Output number:
4
Signal type
PNP
Max current per output:
0.5 A
Max currents sum:
see 8.3 Power supply
Rated impulse with stand voltage U
imp
:
0.8 kV
Rated insulation voltage U
i
:
32 V
Protection against short circuits
Yes
Galvanic insulation:
No
8.8 Semiconductor safety output circuits (OSx)
Output number:
4
Rated operating voltage (0V-24V):
24 Vdc
Signal type
PNP
Max current per signal:
0.5 A
Max currents sum:
2 A
Minimum current:
10 mA
Max. capacity admitted between each
output and ground:
400 nF
Max. inductance admitted per output:
500 mH
Protection fuse:
2 A type gG
Galvanic insulation:
Yes
Rated impulse with stand voltage U
imp
:
0.8 kV
Rated insulation voltage U
i
:
32 V
Short circuit detection between
safety outputs:
Yes
Test pulse length on safety outputs
< 300 µs
8.9 Conforms to the standards
Conforms to the standards:
EN 60947-1, EN 60947-5-1, EN 60204-1, EN
ISO 13849-1, EN ISO 13855, EN 1037, EN ISO
12100, EN ISO 13850, EN 60529, EN 61000-6-
2, EN 61000-6-3, EN 62326-1, EN 61326-1, EN
61326-3-1, EN 60664-1, EN 62061, UL 508, CSA
C22.2 n° 14-95.
Conforms to the directives:
2014/35/EU, 2006/42/EC, 2014/30/EU
Clearance and creepage distances in
accordance with:
EN 60947-1
5/6
10 TERMINALS LAYOUT
11 INTERNAL WIRING DIAGRAM
PWR
O01 O02
I21 I22
O03 O04
OS1 OS2 OS3 OS4
P2
P1
I23 I24
I21
I23 I24
I22
A3 A4
T01
T03 T04
T02
OS1
OS3 OS4
OS2
O01 O02 O03 O04
A1 A2 24V 0V
CS MP207
USB
CH B
C2
CH A
C1
C1 C2
P1
P2
T02 ... T04
T01
OS2
0V
OS3
O02 ... O04
O01
OS4
24V
OS1
A3
A4
C1
C2
A1
A2
I22 ... I24
I21
The module is maintenance free.
9 MAINTENANCE
UL APPROVAL NOTES:
Use 60 or 75 °C copper (CU) conductor and wire size No. 30-12 AWG, stranded or solid. The terminal tightening torque
is 5 – 7 Lb-In. Supply from Remote Class 2 Source or limited voltage limited energy.
Utiliser des conducteurs en cuivre (Cu) 60 ou 75°C rigides ou flexibles de section 30-12 AWG. Couple de serrage des
bornes de 5-7 Lb In. Alimenter avec sources de classes 2 ou avec tension limitée et énergie limitée.