8
- DRR227 -
User manual
5.1 Wiring diagram
DRR227-12ABC
Power Supply
24
23
Switching power supply with extended range
24..230 Vac/dc
±15% 50/60 Hz – 5,5 VA (galvanically insulated)
AN1 Analogue Input
13
14
AI1
TC
Shield/Schermo
For thermocouples K, S, R, J, T, E, N, B.
• Comply with polarity
• For possible extensions, use compensated cable
and terminals suitable for the thermocouples
used(compensated)
• When shielded cable is used, it should be grounded at one
side only
13
14
15
AI1
PT/NI100
Shield/Schermo
Rosso
Red
Bianco
White
Rosso
Red
For thermoresistances PT100, Ni100.
• For the three-wire connection use wires with the same section
• For the two-wire connection short-circuit terminals 1 and 3
• When shielded cable is used, it should be grounded at one
side only
RED
ROSSO
RED
ROSSO
WHITE
BIANCO
13
14
15
14
15
AI1
Shield/Schermo
PT
C/NT
C
For thermoresistances NTC, PTC, PT500, PT1000 and linear
potentiometers
When shielded cable is used, it should be grounded at one
side only to avoid ground loop currents
13
14
16
AI1 V
mA
+Vdc
30 mA
Shield/Schermo
For linear signals in Volt and mA
+Vdc = 12Vdc ±15%/ 30mA
Comply with polarity
When shielded cable is used, it should be grounded at one
side only to avoid ground loop currents