User manual
- DRR245 35
5
up.L.S.
Upper Limit Setpoint
Upper limit selectable for setpoint
-999..+9999
[digit
] (degrees.tenths for temperature sensors),
Default:
1750.
6
LoL.i
Lower Linear Input
Range AN1 lower limit only for linear. Example: with input 4..20 mA this
parameter takes value associated to 4 mA
-999 bis +9999
[digit
],
Default
: 0.
7
up.L.i.
Upper Linear Input
Range AN1 upper limit only for linear. Example: with input 4..20 mA this
parameter takes value associated to 20 mA
-999 bis +9999
[digit
],
Default
: 1000.
8
Latc.
Latch On Function
Automatic setting of limits for linear inputs and potent.
dis.
Disabled (
Default
)
std.
Standard
u.0st.
Virtual zero stored
u.0in
Virtual zero initialized
dYn.L
Allows
to surpass lower and upper limits if on input there are
values out of 0/4..20mA or 0..10V.
9
o.cAL.
Offset Calibration
Value added / subtracted to process visualization (usually correcting the
value of environment temperature)
-999..+1000
[digit
] for linear sensors and potentiometers.
-200.0..+100.0
(degrees.tenths for temperature sensors),
Default
0.0.
10
G.cAL.
Gain Calibration
Percentage value that is multiplied for the process value (allows to
calibrated the working point)
-99.9%..+100.0% (
Default
= 0.0)
ex: to correct the range from 0..1000°C showing 0..1010°C, set the
parameter to -1.0.