Table of Anomaly Signals
If installation malfunctions, controller will switch off regulation output and report
the anomaly. For example, controller will report failure of a connected thermocouple
visualizing
H
(flashing) on display 1 and
SUE
(sensor) on display 2. For other signals,
see table below.
Cause
Do
E-01
((3(
Error in EEPROM cell
programming.
Call Assistance.
E-02
6<6(
Cold junction sensor fault or
room temperature outside of
allowed limits
Call Assistance.
E-04
((3(
Incorrect configuration data.
Possible loss of calibration
values.
Check if the configuration
parameters are correct..
E-05
SUE
Thermocouple open or tempe-
rature outside of limits.
Check the connection with the
sensors and their integrity.
E-08
6<6(
Missing calibration data.
Call Assistance.
12 Configuration
EASY-UP
To simplify the setting of parameters and the integration of the different components
involved in the control system, Pixsys introduces the EASY-UP coding which allows to
set sensors and/or command outputs in one single step.
By means of the code listed in the data sheet enclosed to the sensor or actuator (SSR,
motorized valve, etc.) the EASY-UP coding will set the relevant main parameters on
the controllers (ex. selection of PT100 on parameter “SEN” and the corresponding
measuring range on parameters “Lower and Upper limits of the setpoint”).
Different codes may be entered on the controllers in sequence to configure inputs,
control output or retransmission of signal.
2200 PT100 (-100..500°C); ON/OFF with hysteresis 1°C on Q1; absolute Alarm 1 on Q2
2201 PT100 (-100..500°C); ON/OFF with hysteresis 1°C on SSR; absolute Alarm 1 on Q1
2204 PT1000 (-100..250°C); ON/OFF with hysteresis 1°C on Q1; absolute Alarm 1 on Q2
2205 PT1000 (-100..250°C); ON/OFF with hysteresis 1°C on SSR; absolute Alarm 1 on Q1
2250 PT100 (-100..500°C); PID automatic tune on Q1; absolute Alarm 1 on Q2
2251 PT100 (-100..500°C); PID automatic tune on SSR; absolute Alarm 1 on Q1
2300 TC J (-100..600°C); ON/OFF with hysteresis 1°C on Q1; absolute Alarm 1 on Q2
2301 TC J (-100..600°C); PID automatic tune on SSR; absolute Alarm 1 on Q1
2400 TC K (-100..850°C); ON/OFF with hysteresis 1°C on Q1; absolute Alarm 1 on Q2
2401 TC K (-100..850°C); PID automatic tune on SSR; absolute Alarm 1 on Q1