D900-00-00

2

I56-0003-002R

  

24 Volts 

33 Volts

  

Low 

Med. 

High 

Low 

Med. 

High

 

 

57  61 52 59 61 64

 

 

54  57 60 57 60 62

 

 

53  55 58 55 58 60

 

 

59  61 64 61 63 66

 

 

55  57 60 57 59 62

 

 

54  56 59 56 58 61

 

 

55  57 61 58 60 63

 

 

53  55 58 55 57 60

 

 

52  54 57 54 56 59

 

 

56  58 62 58 60 64

 

 

53  55 58 56 58 62

 

 

54  56 60 56 59 61

 

 

65  68 70 68 70 74

 

 

56  59 62 58 60 64

 

 

54  57 60 56 55 61

 

 

51  52 58 52 54 60

  

8 Volts 

12 Volts

 Tone

 Low 

Med. 

High 

Low 

Med. 

High

  1.2K Repeating 1 Second Chime 

51 

52 

55 

53 

54 

56

  1.0K Repeating 1 Second Chime 

48 

50 

54 

51 

52 

54

  0.8K Repeating 1 Second Chime 

47 

47 

53 

49 

51 

52

  1.2K Repeating 1/4 Second Chime 

53 

54 

58 

55 

57 

59

  1.0K Repeating 1/4 Second Chime 

49 

50 

54 

51 

53 

54

  0.8K Repeating 1/4 Second Chime 

48 

50 

53 

50 

52 

53

  1.2K Temporal 3 Chime 

51 

52 

56 

52 

54 

55

  1.0K Temporal 3 Chime 

48 

49 

54 

49 

51 

51

  0.8K Temporal 3 Chime 

46 

47 

51 

48 

50 

51

  1.2K Single Stroke Chime 

52 

53 

58 

52 

54 

56

  1.0K Single Stroke Chime 

47 

48 

53 

50 

51 

59

  0.8K Single Stroke Chime 

47 

48 

53 

49 

50 

52

  3.0K Continuous Mechanical 

56 

57 

61 

59 

60 

67

  3.0K Temporary Mechanical 

51 

52 

56 

53 

54 

61

  0.5K Continuous Mechanical 

48 

49 

53 

51 

52 

56

  0.5K Temporary Mechanical 

45 

47 

51 

47 

49 

53

SpectrAlert Electronic Chime Sound Output Guide

Chime Selection

Chimes are factory set for high volume, 1000Hz, 1 second chime. Tones
may be selected by making the appropriate settings on the Dip Switch
located on the printed circuit board. The settings required for the available
tone options are as follows:

SpectrAlert Chime Switch Settings

The same number of devices using 12 AWG wire will produce only 2 volts
drop. The same devices using 18 AWG wire will produce 8 volts drop.
Consult your panel manufacturer’s specifications, as well as SpectrAlert’s
operating voltage range to determine acceptable voltage drop.

SpectrAlert Electronic Chime Current Draw*

12VDC:

18–31mA

24VDC:

31–61mA

*Average current draw varies with tones selected. Current ratings per 
System Sensor testing at 12VDC and 24VDC.

SpectrAlert Chime Tones

Repeating 1-Second Chime

Repeating 

1

/

4

-Second Chime

Temporal 3 Chime

Single Stroke Chime

Continuous 500Hz Mechanical and 3kHz mechanical

Temporal 500Hz mechanical and 3kHz mechanical

Scale:
1 second

Switch

1=on 0=off

1

2

3

4

Hz

Type

1

1

1

1

1.2k

Repeating 1 second chime

1

0

1

1

1.0k

Repeating 1 second chime

1

1

0

1

0.8k

Repeating 1 second chime

1

0

0

1

1.2k

Repeating 1/4second chime

1

1

1

0

1.0k

Repeating 1/4second chime

1

0

1

0

0.8k

Repeating 1/4second chime

1

1

0

0

1.2k

Temporal 3 chime

1

0

0

0

1.0k

Temporal 3 chime

0

1

1

1

0.8k

Temporal 3 chime

0

0

1

1

1.2k

Single Stroke Chime

0

1

0

1

1.0k

Single Stroke Chime

0

0

0

1

0.8k

Single Stroke Chime

0

1

1

0

3.0k

Electromechanical Continuous

0

0

1

0

3.0k

Electromechanical Temporal 3

0

1

0

0

0.5k

500 Hz, Continuous

0

0

0

0

0.5K

500 Hz, Temporal 3

VOLUME
SWITCH

5

6

0

0

LOW

1

0

MED

1

1

HIGH

NOTE: Factory default setting is 1.0K Repeating 1 Second Chime set at High volume.