AFP 300/400 I
NSTALLATION
A
ND
P
ROGRAMMING
M
ANUAL
P
AGE
35
C
OPYRIGHT
© 2000, N
OTIFIER
I
NERTIA
P
TY
L
TD
Type Codes (ID’s)
Please Note: when installing detectors the panel will determine the Type code for that detector,
when installing modules, the panel gives a default Type Code, and then the programmer can
determine what Type Code suits the application. The following section shows a table of the
different Type Codes used for Monitor modules and Control Modules.
Monitor Module’s
To install a point see Autoprogram, . To modify a point, See Edit point.
Use the Next and Previous keys to select a code type from the selection list.
Use the arrow and alphanumeric keys to modify the point.
When finished, press <
ENTER
>, and use the Next or Previous keys to select another point to
modify.
Type Codes for Monitor Modules
Type Code Label
Function
MONITOR
(default for MMX-101 & MMX-2) Any alarm module should be given a
MONITOR type ID.
PULL STATION
*Not supported in AUS 3
SMOKE DETECT
*Not supported in AUS 3
HEAT DETECT
*Not supported in AUS 3
Blank (12 spaces)
*Not supported in AUS 3
WATERFLOW
*Not supported in AUS 3
SUPERVISORY
*Not supported in AUS 3
TAMPER
*Not supported in AUS 3
NON FIRE
*Not supported in AUS 3
HAZARD ALERT
*Not supported in AUS 3
FIRE CONTROL
*Not supported in AUS 3
ABORT SWITCH
*Not supported in AUS 3
MAN. RELEASE
*Not supported in AUS 3
SILENCE
*Not supported in AUS 3
SYSTEM RESET
*Not supported in AUS 3
EVACUATE
*Not supported in AUS 3
PAS INHIBIT
*Not supported in AUS 3
TROUBL MONITOR
*Not supported in AUS 3
FAULT MONTOR
*Not supported in AUS 3
MAN REL DLAY
*Not supported in AUS 3
SECOND SHOT
*Not supported in AUS 3
SPRINKLR SYS
*Not supported in AUS 3
COMB. MONITOR
*Not supported in AUS 3
*Important Note:
The Type ID that are not supported by AUS 3 are still
available in verifier but should not be used for programming purposes as they can cause
system failures.
PROGRM
MONITOR
MODULE ADDR 101
Z04 Z Z Z Z M101