Wiring devices on the Loop
Please Note;
Some of the wiring methods used in this manual only apply to the AFP-300/400,
do not adopt these methods on other systems.
Wiring Analogue Addressable Detectors
Note:
If optional shield used, do not connect to the spare terminal on the detector base, join the shield
and insulate it from the other cables.
Wiring Conventional Circuits (MMX-2)
The MMX-2 utilises the 24Vdc Resettable power supply, and the Conventional circuit is
terminated to terminal 6 & 7, with a 3.9k EOL Resistor fitted.
Note:
You must use resettable power on MMX-2’s on an AFP400.
You cannot have AVF on an MMX-2 Module.