Operating, installation and maintenance manual BRUSCHETTA BRU70D - BRU70M
10
8.5
CONNECTION TO AN INSULATED OR DOUBLE-WALL FLUE
The internal dimensions of the external flue pipe must be of minimum 10 x 10 cm, or 10 cm diameter, and of maximum 20 x 20
cm, or 20 cm diameter.
•
By using adequate tools, check that there is a flue draught of at least 12 PA.
•
Only use insulated stainless-steel pipes (double-wall) with a smooth inside lining (flexible stainless steel pipes are not
allowed) securing them to the wall.
•
Allow space for periodic checks and annual cleaning at the lower end of the flue.
•
Connect the stove to the flue by using adequate pipes and fittings.
•
Make absolutely sure to install an anti-draught chimney in compliance with current regulations.
•
It is forbidden to install flues as shown in Figure
8.6
CONNECTION TO THE FLUE
Per un buon funzionamento fare in modo che il raccordo tra stufa e canna fumaria o condotto fumario non sia inferiore al 3% di
inclinazione nei tratti orizzontali. La lunghezza complessiva non deve superare i 2 mt ed il tratto verticale da un raccordo a “T” ad
un altro (cambio di direzione) non deve essere inferiore a 1,5 mt né deve superare i 3 mt. By using adequate tools, check that
there is a flue draught of at least 12 PA. Allow space for periodic checks and annual cleaning at the lower end of the flue.
Connect the stove to the flue by using adequate pipes and fittings. Make absolutely sure to install an anti-draught chimney in
compliance with current regulations.
8.7
CONNECTION TO THE FLUE
The internal dimensions of the flue must be of maximum 20 x 20 cm, or 20 cm diameter. In case of a bigger flue or bad
functioning (cracks, poor insulation, etc.) insert a stainless steel pipe with adequate diameter, for the entire flue length, from the
bottom to the top. By using adequate tools, check that there is a flue draught of at least 12 PA. Connect the stove to the flue by
using adequate pipes and fittings. Make absolutely sure to install an anti-draught chimney in compliance with current regulations.