8
A Indoor unit capacity demand code
Norm code*HP
(9K:1HP,12K:1.2HP,18K:1.5HP)
9
B Indoor unit capacity demand code
10
C Indoor unit capacity demand code
11
D Indoor unit capacity demand code
12
E Indoor unit capacity demand code
13
Outdoor unit amendatory capacity demand code
Forced cooling:7
14
The frequency corresponding to the total indoor
units amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor control
chip
17
A indoor unit evaporator outlet temp.(T
2B
A)
If the temp. is lower than -9 degrees, the digital display digits will show “-9”.If
the temp. is higher than 70 degrees, the digital display digits will show “70”. If
the indoor unit is not connected, the digital display digits will show: “――”
18
B indoor unit evaporator outlet temp.(T
2B
B)
19
C indoor unit evaporator outlet temp.(T
2B
C)
20
D indoor unit evaporator outlet temp.(T
2B
D)
21
E indoor unit evaporator outlet temp.(T
2B
E)
22
A indoor unit room temp.(T
1
A)
If the temp. is lower than 0 degree, the digital display digits will show “0”.If the
temp. is higher than 50 degrees, the digital display digits will show “50”. If the
indoor unit is not connected, the digital display digits will show: “――”
23
B indoor unit room temp.(T
1
B)
24
C indoor unit room temp.(T
1
C)
25
D indoor unit room temp.(T
1
D)
26
E indoor unit room temp.(T
1
E)
27
A indoor unit evaporator temp.(T
2
A)
If the temp. is lower than -9 degrees, the digital display digits will show “-9”.If
the temp. is higher than 70 degrees, the digital display digits will show “70”. If
the indoor unit is not connected, the digital display digits will show: “――”
28
B indoor unit evaporator temp.(T
2
B)
29
C indoor unit evaporator temp.(T
2
C)
30
D indoor unit evaporator temp.(T
2
D)
31
E indoor unit evaporator temp.(T
2
E)
32
Condenser pipe temp.(T3)
33
Outdoor ambient temp.(T4)
34
Compressor discharge temp.(Tp)
The display value is between 30~129 degrees. If the temp. is lower than 30
degrees, the digital display digits will show “30”.If the temp. is higher than 99
degrees, the digital display tube digits will show singles digit and tens digit.
For example, the digital display digits show “0.5”,it means the compressor
discharge temp. is 105 degrees.)
35
AD value of current
The display value is hex number.
For example ,the digital display digits show “Cd”, it means AD value is 205.
36
AD value of voltage
37
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display tube will show singles digit
and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV open angle
is 120×4=480p.)
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
41
EXV open angle for E indoor unit
42
Frequency limit symbol
Bit7
Frequency limit caused by IGBT
radiator
The display value is
hex number. For
example, the digital
display digits show
2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency
limit caused by
T4,T3 and current.
Bit6
Frequency limit caused by PFC
Bit5
Frequency limit caused by T4.
Bit4
Frequency limit caused by T2.
Bit3
Frequency limit caused by T3.
Bit2
Frequency limit caused by Tp.
Bit1
Frequency limit caused by current
Bit0
Frequency limit caused by voltage
Summary of Contents for YN018GMFI16M2D
Page 19: ...7 Wiring Diagrams 8 1 Wiring diagram of DUAL Circuit outdoor unit YN018GMFI16M2D ...
Page 20: ...PCB board of YN018GMFI16M2D ...
Page 21: ...IPM board of YN018GMFI16M2D ...
Page 22: ...8 2 Wiring diagram of Triple Circuit outdoor unit YN027GMFI16M3D YN030GMF16M3D ...
Page 23: ...PCB board of YN030GMFI16M3D ...
Page 24: ...IPM board of YN030GMFI16M3D ...
Page 25: ...PCB board of YN027GMFI16M3D ...
Page 26: ...IPM board of YN027GMFI16M3D ...
Page 27: ...8 3 Wiring diagram of Quadruple 4 zone outdoor unit YN036GMFI16M4D ...
Page 28: ...PCB board of YN036GMFI16M4D ...
Page 29: ...IPM board of YN036GMFI16M4D ...
Page 30: ...PFC board of YN036GMFI16M4D ...
Page 46: ......
Page 48: ...9 4 1 7 Over voltage or too low voltage protection diagnosis and solution ...
Page 60: ...IPM for dual tri zone IPM for quad zone P N for dual tri zone ...
Page 61: ...P N for quad zone ...
Page 62: ...bridge rectifier for dual tri zone bridge rectifier for quad zone ...
Page 63: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Page 65: ...Two ports of the inductance Inductance ...
Page 66: ......
Page 71: ......
Page 73: ......
Page 75: ......
Page 77: ......
Page 89: ...6 EXV check Disconnect the connectors ...
Page 91: ...Red Blue Red Yellow ...
Page 92: ...Brown Orange Brown White ...
Page 108: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Page 122: ...10 Exploded Views Available under a separate document file ...