7.4.4 Electronic Expansion Valve (EXV)
Control
1.EXV will be fully closed when the power is first
turned on. Then EXV will stay at standby with
350P open and will open to target angle after
compressor starts.
2.EXV will close with -160P when compressor
stops. Then EXV will stay at standby with 350P
open and will open to target angle after
compressor starts.
3.The action priority of the EXVs is A-B-C-D.
4.Compressor and outdoor fan start operation
only after EXV is initialized.
7.4.4.1 Cooling mode
The initial open angle of EXV is 250P, adjustment
range is 100-350p. When the unit starts to work
for 3 minutes, the outdoor will receive indoor
units' (of capacity demand) T2B information and
calculate an average of them. After comparing
each indoor’s T2B with the average, the outdoor
gives the following modification commands:
If the T2B
>
average, the relevant valve needs
16p more open;
If the T2B= average, the relevant valve’s open
range remains;
If the T2B
<
average, the relevant valve needs
16p more close.
This modification will be carried out every 2
minutes.
7.4.4.2 Heating mode
The initial open angle of EXV is 250P, adjustment
range is 100-350p.. When the unit starts to work
for 3minutes, the outdoor will receive indoor units'
(of capacity demand) T2 information and
calculate the average of them. After comparing
each indoor’s T2 with the average, the outdoor
gives the following modification commands:
If the T2
>
2, the relevant valve needs
16p more close;
If 2≥the T2≥ average-2, the relevant
valve’s open range remains;
If the T2
<
average-2, the relevant valve needs
16p more open.
This modification will be carried out every 2
minutes.
7.4.5 Four-way valve control
In heating mode, four-way valve is activated. In
defrosting, four-way valve operates in according
to defrosting action. In other modes, four-way
valve is deactivated. When the heating mode to
other modes, the four-way valve goes off after
compressor is off for 2 minutes. Failure or
protection (not including discharge temperature
protection, high and low pressure protection),
four-way valve immediately turns off.
Summary of Contents for YN018GMFI16M2D
Page 19: ...7 Wiring Diagrams 8 1 Wiring diagram of DUAL Circuit outdoor unit YN018GMFI16M2D ...
Page 20: ...PCB board of YN018GMFI16M2D ...
Page 21: ...IPM board of YN018GMFI16M2D ...
Page 22: ...8 2 Wiring diagram of Triple Circuit outdoor unit YN027GMFI16M3D YN030GMF16M3D ...
Page 23: ...PCB board of YN030GMFI16M3D ...
Page 24: ...IPM board of YN030GMFI16M3D ...
Page 25: ...PCB board of YN027GMFI16M3D ...
Page 26: ...IPM board of YN027GMFI16M3D ...
Page 27: ...8 3 Wiring diagram of Quadruple 4 zone outdoor unit YN036GMFI16M4D ...
Page 28: ...PCB board of YN036GMFI16M4D ...
Page 29: ...IPM board of YN036GMFI16M4D ...
Page 30: ...PFC board of YN036GMFI16M4D ...
Page 46: ......
Page 48: ...9 4 1 7 Over voltage or too low voltage protection diagnosis and solution ...
Page 60: ...IPM for dual tri zone IPM for quad zone P N for dual tri zone ...
Page 61: ...P N for quad zone ...
Page 62: ...bridge rectifier for dual tri zone bridge rectifier for quad zone ...
Page 63: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Page 65: ...Two ports of the inductance Inductance ...
Page 66: ......
Page 71: ......
Page 73: ......
Page 75: ......
Page 77: ......
Page 89: ...6 EXV check Disconnect the connectors ...
Page 91: ...Red Blue Red Yellow ...
Page 92: ...Brown Orange Brown White ...
Page 108: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Page 122: ...10 Exploded Views Available under a separate document file ...