55
9.4.10 Inverter compressor drive error diagnosis and solution(P4)
Error Code
P4
Malfunction decision
conditions
An abnormal inverter compressor drive is detected by a special
detection circuit, including communication signal detection,
voltage detection, compressor rotation speed signal detection
and so on.
Supposed causes
Wiring mistake; IPM malfunction; Outdoor fan ass’y faulty
Compressor malfunction; Outdoor PCB faulty
Trouble shooting:
Remark
:
1) 9000 BTU, Heat Pump, 230V model: Measure the
black
pin and
red
pin of the motor connector, the resistance
should be around
385Ω
at 20
℃
(68
℉
)
2) 9000 BTU and 12000 BTU 115 VAC Models, Both Cool Only and Heat Pump: Measure the
black
pin and
red
pin
of the motor connector, the resistance should be around
50Ω
at 20
℃
(68
℉
)
3) 12000 BTU 230 VAC Models, Both Cool Only and Heat Pump: Measure the
black
pin and
red
pin of the motor
connector, the resistance should be around
293Ω
at 20
℃
(68
℉
)
4) 18000 BTU 230 VAC Models, Both Cool Only and Heat Pump: Measure the
black
pin and
red
pin of the motor
connector, the resistance should be around
84.5Ω
at 20
℃
(68
℉
)
5) 24000 BTU 230 VAC Models, Both Cool Only and Heat Pump: Measure the
black
pin and
red
pin of the motor
connector, the resistance should be around
88.5Ω
at 20
℃
(68
℉
)