Technical details
Operating Manual PSSu H m F DP ETH SD
1002323EN04
32
PROFIBUS DP interface
Transmission rate selectable via
automatisch
Connection
9pin female DSub connector
Protocol
DPV0
Operating modes
AutoBaud, Freeze Mode, Set Slave Address, Sync
Mode
Certification
PNO
Description file
Pilz0CB0.gsd
Manufacturer’s ID
0CB0h
Cycle time (t_ExtCo)
2...300 000 ms
Ethernet interface
Number
1
IP address (automatically off)
169.254.X.Y
Connection type
RJ45
Transmission rate
100 MBit/s
Environmental data
Climatic suitability
EN 6006821, EN 60068214, EN 6006822, EN
60068230, EN 60068278
Ambient temperature
Temperature range
0 60 °C
Storage temperature
Temperature range
25 70 °C
Climatic suitability
In accordance with the standard
EN 60068278
Humidity
93 % r. h. at 40 °C
Condensation during operation
Not permitted
EMC
EN 6100042, EN 6100043, EN 6100044, EN
6100045, EN 6100046, EN 6100062, EN
6100064
Vibration
In accordance with the standard
EN 6006826
Frequency
10,0 55,0 Hz
Amplitude
0,35 mm
Acceleration
1g
Shock stress
In accordance with the standard
EN 60068227
Number of shocks
6
Acceleration
15g
Duration
11 ms
In accordance with the standard
EN 60068227
Number of shocks
1000
Acceleration
10g
Duration
16 ms
Max. operating height above sea level
2000 m