Technical details
Operating Manual PSSu H m F DP ETH SD
1002323EN04
30
9
Technical details
General
Approvals
BG, CE, EAC (Eurasian), GOST, TÜV, cULus Lis
ted
Application range
Standard/failsafe
System sections
ST resource
No
FS resource
Yes
ST module bus
Yes
FS module bus
Yes
ST SNp interface
No
FS SNp interface
No
PROFIBUSDP Slave
Yes
IP Connections
IP Connections
Yes
PROFIBUS DP
Yes
Diagnostic Server
No
OPC Server
No
Programming
IEC 61131 programming
No
Multi programming
Yes
Nonvolatile variables
No
Electrical data
Supply voltage
for
Module supply
Voltage
24,0 V
Kind
DC
Voltage tolerance
30 %/+25 %
Max. continuous current that the external power
supply must provide
1,0 A
Output of external power supply (DC)
16,1 W
Supply voltage
for
Periphery supply
Voltage
24 V
Kind
DC
Voltage tolerance
30 %/+25 %
Max. continuous current that the external power
supply must provide
10,0 A
Potential isolation between module supply and peri
phery supply
3050 V
Potential isolation between Module Supply and
PROFIBUS DP
700 V