Analogue inputs
312450
314450
Deviations from the measuring
range limit value
Linearity error
0,05 %
0,05 %
Output variable error at 25
℃
0,2 %
0,2 %
Temperature coefficient
0,0200 %/K
0,0200 %/K
Max. measurement error during
EMC test
2,5 %
2,5 %
Potential isolation between input
and periphery supply
yes
yes
Typ. processing time of the ana-
logue input
1,0 ms
1,0 ms
Inputs
312450
314450
Potential isolation between input
and internal module bus voltage
yes
yes
Environmental data
312450
314450
Climatic suitability
EN 60068-2-1, EN 60068-2-14, EN
60068-2-2, EN 60068-2-30, EN
60068-2-78
EN 60068-2-1, EN 60068-2-14, EN
60068-2-2, EN 60068-2-30, EN
60068-2-78
Ambient temperature
In accordance with the standard
EN 60068-2-14
EN 60068-2-14
Temperature range
0 - 60 °C
-40 - 70 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
EN 60068-2-1/-2
Temperature range
-25 - 70 °C
-40 - 70 °C
Climatic suitability
In accordance with the standard
EN 60068-2-30, EN 60068-2-78
EN 60068-2-30, EN 60068-2-78
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Short-term
EMC
EN 61000-4-2, EN 61000-4-3, EN
61000-4-4, EN 61000-4-5, EN
61000-4-6, EN 61000-6-2, EN
61000-6-4
EN 61000-4-2, EN 61000-4-3, EN
61000-4-4, EN 61000-4-5, EN
61000-4-6, EN 61000-6-2, EN
61000-6-4
Vibration
In accordance with the standard
EN 60068-2-6
EN 60068-2-6
Frequency
10,0 - 150,0 Hz
10,0 - 150,0 Hz
Amplitude
0,35 mm
0,35 mm
Acceleration
1g
1g
Broadband noise
In accordance with the standard –
EN 60068-2-64
Frequency
–
5 - 500 Hz
Acceleration
–
1,9grms