Wiring
Operating Manual PSSu E PS-P +/-10V
21921-EN-03
22
}
Use copper wiring.
6.2
Terminal configuration
Base module
Terminal configuration
Screw terminals:
PSSu BP 1/8 S
PSSu BP 1/8 S-T
Cage clamp terminals:
PSSu BP 1/8 C
PSSu BP 1/8 C-T
Without C-rail:
11-21: 0 V extraction
(11-21 linked internally)
12-22: 0 V infeed
(12-22 linked within the base
module)
13-23: +24 V infeed
(13-23 linked within the base
module)
14: -10 V extraction
24: +10 V extraction
21
11
22
12
23
13
24
14
Screw terminals:
PSSu BP 1/12 S
PSSu BP 1/12 S-T
Cage clamp terminals:
PSSu BP 1/12 C
PSSu BP 1/12 C-T
Without C-rail:
11-21: 0 V extraction
(11-21 linked internally)
12-22: 0 V infeed
(12-22-15-25 linked within
the base module)
13-23: +24 V infeed
(13-23-16-26 linked within
the base module)
14: -10 V extraction
24: +10 V extraction
15-25: 0 V infeed
(12-22-15-25 linked within
the base module)
16-26: +24 V infeed
(13-23-16-26 linked within
the base module)
21
11
22
12
23
13
24
14
26
16
25
15