Commissioning
Operating Manual PSSnet GW1 MODEtherCAT
1002692EN03
32
6.4.1.1
RJ45 connection cable
Fig.: RJ45 connection cable
: RJ45 connector, 8pin
: 100BaseTX cable, max 100 m length
NOTICE
With the plug in connection please note that the data cable and connector
have a limited mechanical load capacity. Appropriate design measures
should be used to ensure that the plugin connection is insensitive to in
creased mechanical stress (e.g. through shock, vibration). Such measures
include fixed routing with strain relief, for example.
6.5
Address setting
6.5.1
IP address setting
The first three bytes of the IP address are: 192.168.0. The last byte of the IP address can
be configured.
The subnet mask is: 255.255.255.0.
The last byte of the IP address is configured using the DIP switches. Value range: 1 ...255.
INFORMATION
The IP address should
only
be set when the module is switched off (no
voltage applied).
The settings are
only
transferred when booting. Any changes made to the
settings during operation will
not
be transferred.
There are various options for setting the last byte of the Gateway's IP address.
1. Use of the DHCP Server is enabled