background image

Overview

Operating Manual PSS u2 ES 16DI
1004551-EN-01

6

2

Overview

Module structure:
A module consists of

}

An electronic module

}

A terminal block with cage clamp terminals and

}

A backplane

The electronic modules are plugged into the backplane and determine the function. The
backplane is used for communication between the head module and the electronic modules
and forms the carrier unit for the electronic modules. The terminal block is plugged into the
electronic modules and is used to connect the field wiring.
Details of the terminal blocks that can be used are available under "Intended Use".

2.1

Module features

Application of the product PSS u2 ES 16DIs:
Electronic module with digital inputs for standard applications
The product has the following features:

}

16 type 3 digital inputs in accordance with IEC 61131-2

}

Configurable input filter time: 0 … 25.5 [ms]

}

Configurable pulse stretching: 0 … 255 [ms]

}

Energy-saving functions

}

LEDs for:
– Status of inputs
– Module error
– Operating status

Summary of Contents for PSS u2 ES 16DI

Page 1: ...PSS u2 ES 16DI Operating Manual 1004551 EN 01 Control system PSS u2 Remote I O system PSS u2...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...9 4 2 Supply 9 4 3 Inputs 9 4 4 Reaction times 12 4 5 Energy saving functions 13 Section 5 Address assignment 14 Section 6 Installation 15 6 1 General installation guidelines 15 6 1 1 Dimensions 15 6...

Page 4: ...ion the product if you have read and understood this document The document should be retained for future ref erence Please refer to the PSS u2 Installation Manual 1 3 Definition of symbols Information...

Page 5: ...on in which the product or devices could be dam aged and also provides information on preventive measures that can be taken It also highlights areas within the text that are of particular import ance...

Page 6: ...or the electronic modules The terminal block is plugged into the electronic modules and is used to connect the field wiring Details of the terminal blocks that can be used are available under Intended...

Page 7: ...d by PASconfig from version 2 0 0 We recommend that you always use the latest version download from www pilz com 3 3 Safety regulations 3 3 1 Use of qualified personnel The products may only be assemb...

Page 8: ...it is intended Damage can be attributed to not having followed the guidelines in the manual Operating personnel are not suitably qualified Any type of modification has been made e g exchanging compon...

Page 9: ...LEDs have two energy saving levels Switching off the LEDs to display the terminal status Switching off the LEDs to display the module and terminal status Standby mode All module functions are inactiv...

Page 10: ...y further Signal requirements at the terminals The 0 signal and the subsequent 1 signal together must be present at the input for longer than twice the configured pulse stretch time tstretch Initialis...

Page 11: ...l Duration of 1 signal tstretch Duration of pulse stretching tsignal_min Time for which a signal must be present at the input in order to be de tected tTRUE Stretched 1 signal in the module tFALSE Str...

Page 12: ...ulse stretching with variable signal duration Legend Clamp Signal at the terminal Pulse stretching Pulse stretching Stretched signal Stretched signal t1 signal Duration of 1 signal tstretch Duration o...

Page 13: ...configurable The module supports the following energy saving levels Switching off the LEDs The LEDs have two energy saving levels Switching off the LEDs to display the terminal status Switching off t...

Page 14: ...assignment The module occupies 2 Byte in the process image PII Meaning State Bit 0 Input data I0 0 0 signal 0 V at the input 1 1 signal 24 V at the input Bit 1 Input data I1 Bit 2 Input data I2 Bit 3...

Page 15: ...arge can damage components Ensure against discharge before touching the product e g by touching an earthed conductive sur face or by wearing an earthed armband 6 1 1 Dimensions The dimensions include...

Page 16: ...ctronic modules may only be plugged or unplugged if the terminal block has been removed first The mechanics of the electronic modules are designed for 20 plug in out cycles 6 2 1 Inserting an electron...

Page 17: ...nstallation Operating Manual PSS u2 ES 16DI 1004551 EN 01 17 3 Insert the terminal block into the suspen sion lug on the module 4 Swivel the terminal block downwards until you hear it click into place...

Page 18: ...rds 6 2 3 Changing an electronic module during operation An electronic module can be hot swapped Effects Module bus communication between the other modules is not interrupted The configuration data is...

Page 19: ...lat head screwdriver Strip the wire back 9 mm Feed the stripped cable as far as it will go into the opening for the spring loaded ter minal Check that the cable is firmly seated Please note The minimu...

Page 20: ...Input I12 14 Input I13 15 Input I14 16 Input I15 ES 16PTD 24 V 1 Voltage output S0 2 Voltage output S1 3 Voltage output S2 4 Voltage output S3 5 Voltage output S4 6 Voltage output S5 7 Voltage output...

Page 21: ...our 2 Meaning Further informa tion Module not ready for operation Green Module ready for operation Green Green Module in operation and there is a 1 signal at the input Green Module in operation and th...

Page 22: ...lue the module sends an all clear Too hot If the module temperature exceeds another threshold value then an error message is sent to the head module the inputs continue to be read and appear in the ST...

Page 23: ...ms Max processing time of input when signal changes from 0 to 1 0 3 ms Min processing time of input when signal changes from 1 to 0 0 005 ms Min processing time of input when signal changes from 0 to...

Page 24: ...rdance with the standard EN 61131 2 Overvoltage category II Pollution degree 2 Protection type In accordance with the standard EN 60529 Housing IP20 Mounting area e g control cabinet IP54 Potential is...

Page 25: ...E1 10 pcs Label holder 23 5 x 10 5 mm 10 pieces 328 910 PSS u2 A LC E2 10 pcs Label holder 103 x 10 5 mm 10 pieces 328 911 PSS u2 A LA E1 10 pcs Labelling strips 23 5 x 10 5 mm 10 x DIN A4 sheet 328 9...

Page 26: ...nual PSS u2 ES 16DI 1004551 EN 01 26 Shield connection element Product type Features Order no PSS u2 A SH 4 Shield connection element for module rack with 4 slots 328 820 PSS u2 A LC B4 Inscription ho...

Reviews: