Wiring
Operating Manual PSS u2 EF 2DO R 8A
1003625-EN-03
| 23
7.2
Terminal configuration
Terminal configuration
Connection examples
1: Output O0.13
3: Potential P0
5: Output O0.14
7: Potential P0
9 Output O1.13
11 Potential P1
13 Output O1.14
15 Potential P1
1-channel actuator
2-channel actuator
1
3
5
7
9
13
15
11
M
1
3
5
7
9
13
15
11
The terminals P0 are interconnected and they many only be used for the outputs O0.13 and
O0.14.
The terminals P1 are interconnected and they many only be used for the outputs O1.13 and
O1.14.
7.3
Function test during commissioning
An error must be simulated for each safety-related output during commissioning: The anti-
cipated error reaction must occur when an output has an error against a supply voltage.
INFORMATION
The safety-related test must be performed on the load and not on the output
terminal.