7. Installation of sensor and actuator is now complete.
1
2
3
4
5
6
7
INFORMATION
Seals (1), (2), (3) meet the requirements of UL 94 V0, seal (4) does
not
meet UL requirements.
Adjustment
}
The safety switch may only be used with the corresponding actuator PSEN ma1.4-03 or
PSEN ma1.4-10.
}
Always test the function with a connected evaluation device.
}
The stated operating distances (see
Technical details [
18]
) only apply when the
safety switch and actuator are installed according to the specifications
Installation [
14]
. Operating distances may deviate if other arrangements are used.
Note the maximum permitted lateral and vertical offset (see
Operating distances and
Lateral and vertical offset [
8]
).
Periodic test
}
Carry out a monthly function test on the safety switch and actuator.
}
Always test the function with a connected evaluation device.
}
The safety function may only be checked by qualified personnel.