PSEN cs4.1n
Operating Manual PSEN cs4.1n
22180-EN-05
14
Teaching in the actuator
Teaching in the actuator for the first time:
The first actuator PSEN cs4.1 detected by the safety switch is automatically taught in as
soon as it is brought into the response range.
To teach in a new actuator:
A maximum of 8 learning procedures are possible.
1. The actuator that is to be taught in must be brought into the safety switch's response
range as the only transponder. As soon as the actuator is detected, the "Safety Gate"
LED will flash yellow.
2. After 20 s has elapsed, the "Safety Gate" LED turns to quick yellow flashes. Trigger a
system reset in the next 120 s by interrupting the power supply.
3. When the supply voltage is switched back on, the learning procedure is complete and
the number of permitted additional learning procedures is reduced by 1.
NOTICE
– The actuator must not be removed during the learning procedure.
– It is no loner possible to reteach his actuator on the same safety
switch.
Installation
CAUTION!
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material. Please check the oper-
ating distances and the assured release distance.
}
The safety switch and actuator should be installed opposite each other in parallel.
}
Actuator PSEN cs4.1: Safety switches and actuators should only be secured using M4
screws with a flat head (e.g. M4 cheese-head or pan head screws).
The actuator should be protected from unauthorised removal and from contamination.
Close the mounting holes using the seals provided. The use of seals should be re-
garded as equivalent to using permanent fastenings in accordance with Clause 7.2c of
EN ISO 14119.
}
Actuator PSEN cs2.1: Safety switches and actuators should be permanently secured
using M5 safety screws with a flat head (e.g. M5 cheese-head or pan head screws).
}
Torque setting: Please note the information provided under
}
The distance between two safety switches must be maintained (see
).
}
Make sure that the safety switch and actuator cannot be used as an end stop.