Pilz PNOZ XV3P Operating Manual Download Page 4

Contents

Operating Manual PNOZ XV3P
20122-EN-05

4

Remove plug-in terminals

34

Order reference

35

EC declaration of conformity

35

Summary of Contents for PNOZ XV3P

Page 1: ...PNOZ XV3P Operating Manual 20122 EN 05 Safety relays...

Page 2: ...umentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Interne...

Page 3: ...personnel 7 Warranty and liability 7 Disposal 7 For your safety 7 Unit features 8 Safety features 8 Block diagram terminal configuration 9 Function Description 9 Operating modes 10 Timing diagram 11...

Page 4: ...Contents Operating Manual PNOZ XV3P 20122 EN 05 4 Remove plug in terminals 34 Order reference 35 EC declaration of conformity 35...

Page 5: ...arly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measure...

Page 6: ...e Technical details 17 NOTICE EMC compliant electrical installation The product is designed for use in an industrial environment The product may cause interference if installed in other environments I...

Page 7: ...s applicable to the specific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended D...

Page 8: ...ed or selectable Possible to cancel delay time LED display for Supply voltage Switch state of the safety contacts Start circuit Plug in connection terminals either spring loaded terminal or screw term...

Page 9: ...2 t are lit Safety contacts 13 14 23 24 33 34 47 48 and 57 58 are closed The unit is active The START LED goes out Input circuit is opened e g E STOP pushbutton operated The LEDs CH 1 and CH 2 go out...

Page 10: ...ts across contacts in the input circuit Dual channel operation without detection of shorts across contacts Redundant input circuit detects PNOZ XV3P earth faults in the start and input circuit short c...

Page 11: ...ay on de energisation t3 Waiting period with a monitored start t4 Recovery time tv Delay time NOTICE At the latest the delay on de energisation safety contacts open after the set delay time 50 ms 15 o...

Page 12: ...en used previously with high cur rents When connecting magnetically operated reed proximity switches ensure that the max peak inrush current on the input circuit does not overload the proximity switch...

Page 13: ...tection of shorts across contacts S1 S22 S31 S32 S21 S12 S11 Safety gate without detection of shorts across contacts S1 S22 S21 S12 S32 S11 S31 S1 S2 S22 S21 S11 S12 S32 Safety gate with detection of...

Page 14: ...start up test Automatic start S33 S34 S13 S14 S33 S13 S34 S14 Simultaneity S1 and S2 max 3 s Monitored start S33 S34 S3 S14 S13 NOTICE In the event of an automatic start The unit starts up automatica...

Page 15: ...f the machine plant for SIL CL 3 PL e at least 1x per month for SIL CL 2 PL d at least 1x per year Follow the instructions below Activate the safety function and check whether all the used safety cont...

Page 16: ...he cause of the respective fault has been rectified and the supply voltage is switched off for approx 1 minute the unit is ready for operation again Contact malfunctions If the contacts have welded re...

Page 17: ...cycle 100 100 100 Max inrush current im pulse Current pulse A1 5 A 5 A 5 A Pulse duration A1 1 ms 1 ms 1 ms Inputs 777510 777512 777514 Number 2 2 2 Voltage at Input circuit DC 24 V 24 V 24 V Start c...

Page 18: ...01 A Max current 8 A 8 A 8 A Max power 200 W 200 W 200 W Utilisation category of safety contacts delayed AC1 at 240 V 240 V 240 V Min current 0 01 A 0 01 A 0 01 A Max current 8 A 8 A 8 A Max power 20...

Page 19: ...10 A 10 A 10 A Circuit breaker 24V AC DC characteristic B C 6 A 6 A 6 A External contact fuse pro tection delayed safety contacts Max melting integral 240 A s 240 A s 240 A s Blow out fuse quick 10 A...

Page 20: ...s 0 5 s 1 s 2 s 4 s 6 s 8 s 10 s 15 s 20 s 25 s 30 s 0 1 s 0 2 s 0 3 s 0 4 s 0 5 s 0 6 s 0 7 s 0 8 s 1 s 1 5 s 2 s 3 s 0 5 s Time accuracy 15 15 50 ms 15 15 50 ms 15 15 50 ms Repetition accuracy 2 2...

Page 21: ...0 cycles Material Bottom PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Front ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V0 Top PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Connection type Screw terminal Screw terminal Sc...

Page 22: ...0 100 100 Max inrush current im pulse Current pulse A1 5 A 5 A 5 A Pulse duration A1 1 ms 1 ms 1 ms Inputs 777515 777517 777518 Number 2 2 2 Voltage at Input circuit DC 24 V 24 V 24 V Start circuit DC...

Page 23: ...01 A Max current 8 A 8 A 8 A Max power 200 W 200 W 200 W Utilisation category of safety contacts delayed AC1 at 240 V 240 V 240 V Min current 0 01 A 0 01 A 0 01 A Max current 8 A 8 A 8 A Max power 20...

Page 24: ...10 A 10 A 10 A Circuit breaker 24V AC DC characteristic B C 6 A 6 A 6 A External contact fuse pro tection delayed safety contacts Max melting integral 240 A s 240 A s 240 A s Blow out fuse quick 10 A...

Page 25: ...ms 250 ms Delay time tv 3 s 10 s 0 3 s 5 s 10 s 20 s 40 s 60 s 80 s 100 s 150 s 200 s 250 s 300 s Time accuracy 15 15 50 ms 15 15 50 ms 15 15 50 ms Repetition accuracy 2 2 2 Waiting period with a moni...

Page 26: ...0 cycles Material Bottom PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Front ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V0 Top PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Connection type Screw terminal Screw terminal Sc...

Page 27: ...rush current im pulse Current pulse A1 5 A 5 A 5 A Pulse duration A1 1 ms 1 ms 1 ms Inputs 787510 787512 787518 Number 2 2 2 Voltage at Input circuit DC 24 V 24 V 24 V Start circuit DC 24 V 24 V 24 V...

Page 28: ...01 A Max current 8 A 8 A 8 A Max power 200 W 200 W 200 W Utilisation category of safety contacts delayed AC1 at 240 V 240 V 240 V Min current 0 01 A 0 01 A 0 01 A Max current 8 A 8 A 8 A Max power 20...

Page 29: ...10 A 10 A 10 A Circuit breaker 24V AC DC characteristic B C 6 A 6 A 6 A External contact fuse pro tection delayed safety contacts Max melting integral 240 A s 240 A s 240 A s Blow out fuse quick 10 A...

Page 30: ...0 s 15 s 20 s 25 s 30 s 0 1 s 0 2 s 0 3 s 0 4 s 0 5 s 0 6 s 0 7 s 0 8 s 1 s 1 5 s 2 s 3 s 0 3 s 5 s 10 s 20 s 40 s 60 s 80 s 100 s 150 s 200 s 250 s 300 s Time accuracy 15 15 50 ms 15 15 50 ms 15 15 5...

Page 31: ...8 Mounting position Any Any Any Mechanical life 10 000 000 cycles 10 000 000 cycles 10 000 000 cycles Material Bottom PPO UL 94 V0 PPO UL 94 V0 PPO UL 94 V0 Front ABS UL 94 V0 ABS UL 94 V0 ABS UL 94 V...

Page 32: ...ulating the safety characteristic data INFORMATION A safety function s SIL PL values are not identical to the SIL PL values of the units that are used and may be different We recommend that you use th...

Page 33: ...witching current A Example Inductive load 0 2 A Utilisation category AC15 Contact service life 4 000 000 cycles Provided the application to be implemented requires fewer than 4 000 000 cycles the PFH...

Page 34: ...ting Manual PNOZ XV3P 20122 EN 05 34 Remove plug in terminals Procedure Insert the screwdriver into the housing recess behind the terminal and lever the terminal out Do not remove the terminals by pul...

Page 35: ...VDC Delay up to 30 s selectable Spring loaded terminals 787 510 PNOZ XV3P 24 VDC Delay up to 30 s selectable Screw terminals 777 510 PNOZ XV3P C 24 VDC Delay up to 300 s selectable Spring loaded term...

Page 36: ...T p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document dependi...