PNOZ XV3.3P
Operating Manual PNOZ XV3.3P
20777-EN-09
| 19
Times
777511
787511
Repetition accuracy
2 %
2 %
Waiting period with a monitored
start
300 ms
300 ms
Min. start pulse duration with a
monitored start
30 ms
30 ms
Supply interruption before de-ener-
gisation
20 ms
20 ms
Simultaneity, channel 1 and 2 max.
∞
∞
Environmental data
777511
787511
Climatic suitability
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Not permitted
EMC
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
Vibration
In accordance with the standard
EN 60068-2-6
EN 60068-2-6
Frequency
10 - 55 Hz
10 - 55 Hz
Amplitude
0,35 mm
0,35 mm
Airgap creepage
In accordance with the standard
EN 60947-1
EN 60947-1
Overvoltage category
III / II
III / II
Pollution degree
2
2
Rated insulation voltage
250 V
250 V
Rated impulse withstand voltage
4 kV
4 kV
Protection type
Housing
IP40
IP40
Terminals
IP20
IP20
Mounting area (e.g. control cab-
inet)
IP54
IP54
Mechanical data
777511
787511
Mounting position
Any
Any
Mechanical life
10,000,000 cycles
10,000,000 cycles
Material
Bottom
PPO UL 94 V0
PPO UL 94 V0
Front
ABS UL 94 V0
ABS UL 94 V0
Top
PPO UL 94 V0
PPO UL 94 V0
Connection type
Screw terminal
Spring-loaded terminal
Mounting type
plug-in
plug-in