Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}
When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket
or end angle).
Wiring
Please note:
}
" must be followed.
}
Output 13-14 is a safety contact, output 21-22 is an auxiliary contacts (e.g. for display).
}
Auxiliary contact 21-22 should
not
be used for safety circuits!
}
Do not connect undesignated terminals.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
}
Calculation of the max. cable length l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see
)
R
l
/ km = cable resistance/km
}
Use copper wiring with a temperature stability of 60/75 °C.
}
To prevent EMC interferences (particularly common-mode interferences) the measures
described in EN 60204-1 must be executed. This includes the separate routing of cables
of the control circuits (input, start and feedback loop) from other cables for energy trans-
mission or the shielding of cables, for example.
}
Adequate protection must be provided on all output contacts with capacitive and inductive
loads.
}
Do not switch low currents using contacts that have been used previously with high cur-
rents.
}
The power supply must comply with the regulations for extra low voltages with protective
electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.