PNOZ X7.1
Operating Manual PNOZ X7.1
21003-EN-06
| 15
Relay outputs
External contact fuse protection, auxiliary contacts
Max. melting integral
240 A²s
Blow-out fuse, quick
6 A
Blow-out fuse, slow
4 A
Blow-out fuse, gG
6 A
Circuit breaker 24 V AC/DC, characteristic B/C
4 A
Conventional thermal current
6 A
Contact material
0,2 µm Au
Times
Switch-on delay
With automatic start typ.
50 ms
With automatic start max.
150 ms
With automatic start after power on typ.
50 ms
With automatic start after power on max.
150 ms
With manual start typ.
35 ms
With manual start max.
150 ms
Delay-on de-energisation
With E-STOP typ.
45 ms
With E-STOP max.
70 ms
With power failure typ.
45 ms
With power failure max.
70 ms
Recovery time at max. switching frequency 1/s
After E-STOP
50 ms
After power failure
150 ms
Supply interruption before de-energisation
20 ms
Environmental data
Climatic suitability
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
Condensation during operation
Not permitted
EMC
EN 60947-5-1, EN 61000-6-2, EN 61326-3-1
Vibration
In accordance with the standard
EN 60068-2-6
Frequency
10 - 55 Hz
Amplitude
0,35 mm
Airgap creepage
In accordance with the standard
EN 60947-1
Overvoltage category
III / II
Pollution degree
2
Rated insulation voltage
250 V
Rated impulse withstand voltage
4 kV