PNOZ V
Operating Manual PNOZ V
21115-EN-07
| 16
Relay outputs
774789
774790
774791
Utilisation category of
safety contacts delayed
AC15 at
230 V
230 V
230 V
Max. current
4 A
4 A
4 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
4 A
4 A
4 A
Utilisation category of
auxiliary contacts
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A
Utilisation category in ac-
cordance with UL
Voltage
240 V AC G. P.
240 V AC G. P.
240 V AC G. P.
With current
8 A
8 A
8 A
Voltage
24 V DC Resistive
24 V DC Resistive
24 V DC Resistive
With current
5 A
5 A
5 A
Pilot Duty
C300, R300
C300, R300
C300, R300
External contact fuse pro-
tection, safety contacts
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
10 A
Blow-out fuse, slow
6 A
6 A
6 A
Blow-out fuse, gG
10 A
10 A
10 A
Circuit breaker 24V
AC/DC, characteristic
B/C
6 A
6 A
6 A
External contact fuse pro-
tection, delayed safety
contacts
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
6 A
6 A
6 A
Blow-out fuse, slow
4 A
4 A
4 A
Blow-out fuse, gG
6 A
6 A
6 A
Circuit breaker 24 V
AC/DC, characteristic
B/C
4 A
4 A
4 A