6.1.3
Supply voltage for device
Requirements:
}
When selecting the power supply, please refer to the requirements stated under “Tech
nical Details”.
Make sure that the supply voltage for the power circuits (B1/B2) complies with the spe
cified tolerance of +/10 %. If the voltage is outside this tolerance, then
–
the device will change to a fault condition, if the outputs are switched on
–
a message will be entered in the error stack if the outputs are switched off.
}
The power supply must be able to bridge a power outage of 20 ms.
WARNING!
Electric shock!
Safe electrical isolation must be ensured for the external power supply that
generates the supply voltage. Failure to do so could result in electric shock.
The power supplies must comply with EN 609501, 05/2006, EN 6155826,
11/1997.
Supply voltage to the device
Please note: The supply
voltage must be protected
with a fuse.
Fuse F1:
Circuit breaker, 24 VDC, 4 A,
characteristic B/C
L3
L1
L2
PE
A1
A2
L+
L-
F1
6.1.4
Supply voltage for power circuits
Requirements:
}
When selecting the power supply, please refer to the requirements stated under “Tech
nical Details”.
Make sure that the supply voltage for the power circuits (B1/B2) complies with the spe
cified tolerance of +/10 %. If the voltage is outside this tolerance, then
–
the device will change to a fault condition, if the outputs are switched on
–
a message will be entered in the error stack if the outputs are switched off.
}
The power supply must be able to bridge a power outage of 20 ms.