Commissioning
Operating Manual PNOZ ms2p TTL
1001722-EN-03
19
6.2
Pin assignment of RJ45 socket
RJ45 socket
8-pin
PIN
Track
8 1
1
n.c.
2
0 V
3
n.c.
4
A
5
/A
6
n.c.
7
B
8
/B
6.3
Connection of proximity switches
Proceed as follows when connecting proximity switches:
}
Terminals I10 and I11: connect the proximity switch for axis 1
}
Terminals I20 and I21: connect the proximity switch for axis 2.
}
If only one axis is to be monitored, either terminals I10 and I11 or terminals I20 and I21
will remain free.
}
When connecting incremental encoders and proximity switches on one axis:
– Terminals I10: connect proximity switch for axis 1 (I11 is not used)
– Terminals I20: connect proximity switch for axis 2 (I21 is not used)
}
The proximity switch must always be connected to a 0 V terminal of the speed monitor.
The 0 V terminals are connected internally.
}
Connect proximity switch to 24 VDC of the power supply or the speed monitor (the 24 V
terminals of the speed monitor are connected internally)
I20
I11
I21
I10
0 V
L+
L-