Commissioning
Operating Manual PNOZ mc12p
1003016-EN-03
14
6
Commissioning
6.1
Wiring
The wiring is defined in the circuit diagram of the PNOZmulti Configurator. It is possible to
define which inputs and outputs on the safety system will communicate with Ethernet
POWERLINK.
Please note:
}
Information given in the
Technical details [
17]
must be followed.
}
Use copper wiring with a temperature stability of 75 °C.
Please note the following when connecting to Ethernet POWERLINK:
}
The following minimum requirements of the connection cable and connector must be
met:
– Only use standard industrial Ethernet cable and connectors.
– Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
– 100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
}
Measures to protect against interference:
Ensure the requirements for the industrial use of Ethernet POWERLINK are met, as
stated in the Installation Manual published by the User Group.
CAUTION!
Only connect and disconnect the expansion module when the supply
voltage is switched off.
6.2
Interface assignment
RJ45 socket
8-pin
PIN
Standard
8 1
1
TD+ (T)
2
TD- (Transmit-)
3
RD+ ()
4
n.c.
5
n.c.
6
RD- (Receive-)
7
n.c.
8
n.c.
n.c.: Not connected