background image

Commissioning

Operating Manual PNOZ m ES Profinet
1003386­EN­02

15

6

Commissioning

6.1

General wiring guidelines

The wiring is defined in the circuit diagram of the PNOZmulti Configurator. It is possible to
define which inputs and outputs on the safety system will communicate with PROFINET.

Please note:

}

Information given in the "

Technical details [

 20]

" must be followed.

}

Use copper wiring with a temperature stability of 75 °C.

Please note the following when connecting to PROFINET:

}

The following minimum requirements of the connection cable and connector must be
met:

Only use standard industrial Ethernet cable and connectors.

Only use double­shielded twisted pair cable and shielded RJ45 connectors (indus­
trial connectors).

100BaseTX cable in accordance with the Ethernet standard (min. Category 5)

}

Measures to protect against interference:

Ensure the requirements for the industrial use of PROFINET are met, as stated in the
Installation Manual published by the User Group.

}

External measures must be used to connect the terminal 

 to the functional earth,

when the mounting rail is 

not

 connected to the functional earth.

}

Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.

}

The power supply must meet the regulations for extra low voltages with protective sep­
aration.

CAUTION!

Only connect and disconnect the expansion module when the supply
voltage is switched off.

NOTICE

When installing, you must refer to the guidelines published by the
RPOFIBUS & PROFINET International (PI) User Group.

6.2

Connecting the supply voltage

Connect the supply voltage to the fieldbus module:

}

Terminal 

24 V

: + 24 V DC

}

Terminal 

0 V

: 0 V

Summary of Contents for PNOZ m ES Profinet

Page 1: ...PNOZ m ES Profinet Operating Manual 1003386 EN 02 Configurable Control System PNOZmulti...

Page 2: ...es may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the s...

Page 3: ...nction description 11 4 1 Operation 11 4 2 Data access 11 4 3 Assigning the inputs outputs in the PNOZmulti Configurator to the PROFINET inputs outputs 12 4 4 Block diagram 12 Section 5 Installation 1...

Page 4: ...Content Operating Manual PNOZ m ES Profinet 1003386 EN 02 4 Section 9 Order reference 22 9 1 Module 22 9 2 Accessories 22...

Page 5: ...on that is particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates...

Page 6: ...Introduction Operating Manual PNOZ m ES Profinet 1003386 EN 02 6 INFORMATION This gives advice on applications and provides information on special fea tures...

Page 7: ...inputs and outputs on the control system PNOZmulti 2 can be defined in the PNOZmulti Configurator for communication with the fieldbus PROFINET Transmission rate 100 MBit s 100BaseTX full and half dupl...

Page 8: ...Overview Operating Manual PNOZ m ES Profinet 1003386 EN 02 8 2 3 Front view Legend X1 X2 Profinet interfaces 0 V 24 V Supply connections Functional earth LED Power Run Diag L A 1 L A 2...

Page 9: ...OZmulti System Expansion for de tails of the base units that can be connected The configurable control system PNOZmulti 2 is used for the safety related interruption of safety circuits and is designed...

Page 10: ...y and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed t...

Page 11: ...GSDML file is available on the Internet at www pilz de 4 2 Data access The data is structured as follows Virtual data Input area PNOZ m ES Profinet The values for the inputs are set as an output in th...

Page 12: ...this way Input data The Master writes to the virtual inputs of the PNOZmulti 2 Description Input data from PNOZmulti 2 Virtual inputs i0 i31 4 Input Bytes Virtual inputs i32 i63 4 Input Bytes Virtual...

Page 13: ...g rail To comply with EMC requirements the mounting rail must have a low impedance con nection to the control cabinet housing The ambient temperature of the PNOZmulti units in the control cabinet must...

Page 14: ...Installation Operating Manual PNOZ m ES Profinet 1003386 EN 02 14 5 3 Dimensions 101 4 4 11 115 0 4 53 22 5 0 88...

Page 15: ...ith the Ethernet standard min Category 5 Measures to protect against interference Ensure the requirements for the industrial use of PROFINET are met as stated in the Installation Manual published by t...

Page 16: ...roject must be amended using the PNOZmulti Configurator Proceed as described in the operat ing instructions for the base unit NOTICE For the commissioning and after every program change you must check...

Page 17: ...Commissioning Operating Manual PNOZ m ES Profinet 1003386 EN 02 17 6 5 Connection example PROFINET Device 1 PROFINET Device 2 PROFINET Device 3 PROFINET Controller...

Page 18: ...of 30 s the expansion module PNOZ m ES Profinet connects to the IO controller and RUN status is displayed on PROFINET The error message No Con nection with Base Module is sent to the IO controller Le...

Page 19: ...3386 EN 02 19 LED Meaning L A1 Green Bus connection available at X1 Green Data traffic present at X1 Bus connection is not available at X1 L A2 Green Bus connection available at X2 Green Data traffic...

Page 20: ...onnection 2 x RJ45 Galvanic isolation Yes Environmental data Ambient temperature In accordance with the standard EN 60068 2 14 Temperature range 0 60 C Forced convection in control cabinet off 55 C St...

Page 21: ...op hat rail DIN rail Top hat rail 35 x 7 5 EN 50022 Recess width 27 mm Material Bottom PC Front PC Top PC Green Conductor cross section with screw terminals 1 core flexible 0 25 2 50 mm 24 12 AWG 2 co...

Page 22: ...pe Features Order no PNOZ mm0 xp connector left Jumper yellow black to connect the modules 1 piece 779 260 Connection terminals Product type Features Order no Spring terminals PNOZ mmcxp 1 pc Spring l...

Page 23: ...mo PMCprotego PMCtendo PMD PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would poi...

Reviews: