PNOZ c2

Operating Manual PNOZ c2
22212­EN­02

8

NOTICE

It must 

not 

be possible to disconnect the supply voltage of PNOZ c2 and

the supply voltage for the safe sensor or light guard separately.

*

 When operating with a light guard: Use the free connections A1 and A2 for

connecting the supply voltage of the sender.

Start circuit/feedback loop

Start circuit

Feedback loop

automatic start

monitored start

NOTICE

The unit automatically starts when the start circuit S33­S35 is overridden.
Use external circuit measures to prevent an unexpected restart.

Semiconductor output

*Connect together the 0V connections on all the external power supplies

Summary of Contents for PNOZ c2

Page 1: ...PNOZ c2 Operating Manual 22212 EN 02 Safety relays...

Page 2: ...KG Copies may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET...

Page 3: ...r your safety 5 Unit features 5 Safety features 6 Block diagram terminal configuration 6 Function description 6 Installation 7 Wiring 7 Preparing for operation 7 Operation 9 Status indicators 9 Faults...

Page 4: ...This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken WARNING This warning must b...

Page 5: ...with the documented technical details For your safety Only install and commission the unit if you have read and understood these operating instructions and are familiar with the applicable regulation...

Page 6: ...The unit is ready for operation when the start circuit is closed or when a start contact is opened and closed again in the start circuit High signal at input circuit e g light guard nor interrupted Th...

Page 7: ...welding a fuse should be connected before the output contacts see Technical details Use copper wire that can withstand 60 75 C Do not connect capacitive load The power supply must comply with the reg...

Page 8: ...ht guard Use the free connections A1 and A2 for connecting the supply voltage of the sender Start circuit feedback loop Start circuit Feedback loop automatic start monitored start NOTICE The unit auto...

Page 9: ...ircuit has opened Technical details General 710002 Approvals CCC CE EAC Eurasian T V cULus Listed Electrical data 710002 Supply voltage Voltage 24 V Kind DC Voltage tolerance 20 20 Output of external...

Page 10: ...contacts DC 1 at 24 V Max current 4 0 A Min current 0 01 A Max power 100 W Utilisation category In accordance with the standard EN 60947 5 1 Safety contacts AC15 at 230 V Max current 1 5 A Safety con...

Page 11: ...0 ms Simultaneity channel 1 and 2 Environmental data 710002 Climatic suitability EN 60068 2 78 Ambient temperature Temperature range 10 55 C Storage temperature Temperature range 40 85 C EMC EN 60947...

Page 12: ...62061 SIL CL EN IEC 62061 PFHD 1 h IEC 61511 SIL IEC 61511 PFD EN ISO 13849 1 2008 TM year Safety con tacts in stantaneous PL e Cat 4 SIL CL 3 2 31E 09 SIL 3 2 03E 06 20 INFORMATION All the units use...

Page 13: ...on the relay output If the service life graphs are not accessible the stated PFH value can be used irrespective of the switching frequency and the load as the PFH value already considers the relay s B...

Page 14: ...must be provided on all output contacts With DC contactors use flywheel diodes for spark suppression Order reference Type Features Terminals Order no PNOZ c2 24 VDC With spring loaded terminals 710 0...

Page 15: ...raNET p Pilz PIT PMCprotego PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would po...