PNOZ po3.3p
Operating Manual PNOZ po3.3p
20678-EN-07
12
}
A welded contact fuse protection of PNOZ po3.3p must be provided in order to meet
the safety function of PNOZ po3.3p in accordance with EN ISO 13849-1, PL e (Cat. 4).
Motor output
Manufacturer, type
Test voltage 3 x 420 V AC
Manufacturer, type
Test voltage 3 x 480 V AC
3 kW
ABB MS 325-9
Moeller PKZM0-6,3
Telemecanique GV2-LE14
ABB MS 325-6.3
Moeller PKZM0-6,3
Telemecanique GV2-LE10
4 kW
ABB MS 325-9
Moeller PKZM0-10
Telemecanique GV2-LE14
ABB MS 325-9
Moeller PKZM0-10
5.5 kW
ABB MS 325-12.5
Moeller PKZM0-10
---
}
Further information on request
}
Manufacturer's details have to be noted in addition to the specifications in the coordina-
tion tables.
}
With smaller motor outputs a relevant motor protection switch has to be selected fro the
catalogues of one of the manufacturers mentioned above.
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Status indicators
LEDs indicate the status and errors during operation:
LED on
POWER
Supply voltage is present.
CH.1
Safety contacts of channel 1 are closed.
CH.2
Safety contacts of channel 2 are closed.
FAULT
Contact malfunction