Wiring

Please note:

}

Information given in the "

Technical details [

 12]

" must be followed.

}

The wiring guidelines in the base units' operating instructions must be taken into ac-
count.

}

Outputs 13-14, 23-24, 33-34 are safety contacts; output 41-42 is an auxiliary contact
(e.g. for display).

}

Auxiliary contact 41-42 should 

not

 be used for safety circuits!

}

To prevent contact welding, a fuse should be connected before the output contacts (see

Technical details [

 12]

).

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.

}

Ensure the wiring and EMC requirements of EN 60204-1 are met.

Preparing for operation

Connection

AC

DC

Supply voltage/input circuit/feed-
back loop

Interface

PNOZsigma

PNOZ s30/
PNOZ mm0.1p
PNOZ mm0.2p

PNOZs22

Connection to speed monitor
PNOZ s30/PNOZmulti Mini
base unit

Base unit: Speed monitor PNOZ
s30

Base unit: Small control system
PNOZmulti Mini

The feedback loop is connected
and evaluated via the connector

PNOZ s30

PNOZmulti Mini 
base unit

PNOZsigma 
expansion 
module

Summary of Contents for 750132

Page 1: ...PNOZ s22 Operating Manual 22170 EN 04 Safety relays...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...7 Use of qualified personnel 7 Warranty and liability 7 Disposal 7 For your safety 8 Unit features 8 Safety features 8 Block diagram terminal configuration 9 Function description 9 Installation 9 Wiri...

Page 4: ...Contents Operating Manual PNOZ s22 22170 EN 04 4 Permitted operating height 19 Remove plug in terminals 20 Order reference 20 EC declaration of conformity 20...

Page 5: ...ly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures...

Page 6: ...elated characteristic values stated under safety related character istic data can only be achieved if the base unit also exhibits these values The following is deemed improper use in particular Any co...

Page 7: ...s systems and machines the person has to be informed of the state of the art and the applicable national European and international laws directives and standards It is the company s responsibility onl...

Page 8: ...controlled separately LED indicator for Input state of channel Ext 1 O0 Input state of channel Ext 2 O1 Plug in connection terminals either spring loaded terminal or screw terminal See order referenc...

Page 9: ...rately Installation Connect the contact expansion block to the PNOZ s30 or base unit PNOZ mm0 1p PNOZ mm0 2p Connect the contact expansion block using the connector supplied Control cabinet installati...

Page 10: ...t contacts see Technical details 12 Use copper wire that can withstand 60 75 C Sufficient fuse protection must be provided on all output contacts with capacitive and in ductive loads Ensure the wiring...

Page 11: ...safety contacts switch off output and start the device again so that the internal diagnostics can check that the safety contacts open correctly for SIL CL 3 PL e at least 1x per month for SIL CL 2 PL...

Page 12: ...sted Electrical data 750132 751132 Supply voltage Voltage tolerance 15 20 15 20 Supply voltage Voltage 24 V 24 V Kind DC DC Power consumption 1 5 W 1 5 W Duty cycle 100 100 Relay outputs 750132 751132...

Page 13: ...A 1500 VA DC1 at 24 V 24 V Min current 0 01 A 0 01 A Max current 6 A 6 A Max power 150 W 150 W Utilisation category In accordance with the standard EN 60947 5 1 EN 60947 5 1 Utilisation category of sa...

Page 14: ...rmal current while loading several contacts 750132 751132 Ith per contact at UB DC AC1 240 V DC1 24 V Conv therm current with 1 con tact 6 A 6 A Conv therm current with 2 con tacts 5 A 5 A Conv therm...

Page 15: ...cycles Material Bottom PC PC Front PC PC Top PC PC Connection type Screw terminal Spring loaded terminal Mounting type plug in plug in Conductor cross section with screw terminals 1 core flexible 0 2...

Page 16: ...1 6 A 2 6 A 3 5 A Safety characteristic data Operating Mode EN ISO 13849 1 2015 PL EN ISO 13849 1 2015 Category EN 62061 SIL CL EN 62061 PFHD 1 h IEC 61511 SIL IEC 61511 PFD EN ISO 13849 1 2015 TM yea...

Page 17: ...ut If the service life graphs are not accessible the stated PFH value can be used irrespective of the switching frequency and the load as the PFH value already considers the relay s B10d value as well...

Page 18: ...e life 1 000 000 cycles Provided the application to be implemented requires fewer than 1 000 000 cycles the PFH value see Technical details 12 can be used in the calculation To increase the service li...

Page 19: ...e category Max rated impulse withstand voltage 3000 m 150 V II 2 5 kV 100 V III 2 5 kV 4000 m 150 V II 2 5 kV 100 V III 2 5 kV 5000 m 150 V II 2 5 kV 100 V III 2 5 kV Reduction of rated insulation vol...

Page 20: ...nection type Order No PNOZ s22 24 VDC Screw terminals 750 132 PNOZ s22 C 24 VDC Spring loaded terminals 751 132 EC declaration of conformity This product these products meet the requirements of the di...

Page 21: ...yNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depe...

Reviews: