PNOZ s9
Operating Manual PNOZ s9
21401-EN-10
22
Relay outputs
750109
751109
751189
Utilisation category in ac-
cordance with UL
Voltage
240 V AC G.U. (same po-
larity)
240 V AC G.U. (same po-
larity)
240 V AC G.U. (same po-
larity)
With current
6 A
6 A
6 A
Voltage
24 V DC G. U.
24 V DC G. U.
24 V DC G. U.
With current
6 A
6 A
6 A
External contact fuse pro-
tection, safety contacts
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Max. melting integral
260 A²s
260 A²s
260 A²s
Blow-out fuse, quick
10 A
10 A
10 A
Blow-out fuse, slow
6 A
6 A
6 A
Blow-out fuse, gG
10 A
10 A
10 A
Circuit breaker 24V
AC/DC, characteristic
B/C
6 A
6 A
6 A
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral
160 A²s
160 A²s
160 A²s
Blow-out fuse, quick
10 A
10 A
10 A
Blow-out fuse, slow
6 A
6 A
6 A
Blow-out fuse, gG
6 A
6 A
6 A
Circuit breaker 24 V
AC/DC, characteristic
B/C
6 A
6 A
6 A
Conventional thermal cur-
rent
6 A
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
0,2 µm Au
Times
750109
751109
751189
Switch-on delay
With manual start typ.
60 ms
60 ms
60 ms
With manual start max.
80 ms
80 ms
80 ms
Delay-on de-energisation
With E-STOP typ.
40 ms
40 ms
40 ms
With E-STOP max.
50 ms
50 ms
50 ms
Recovery time at max.
switching frequency 1/s
After power failure
800 ms
800 ms
800 ms