PSEN cs2.2n
Operating Manual PSEN cs2.2n
1003367-EN-04
13
Installation
CAUTION!
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material. Please check the oper-
ating distances and the assured release distance.
}
The safety switch and actuator should be installed opposite each other in parallel.
– Make sure that the actuator is aligned to the marking on the sensor that guarantees
the operating distance required by the plant design (see
Operating
distances [
8]
).
}
Safety switches and actuators should be permanently secured using M5 safety screws
with a flat head (e.g. M5 cheese-head or pan head screws).
}
Protect the actuator from contamination.
}
Torque setting: Please note the information provided under
Technical details [
17]
.
}
The distance between two safety switches must be maintained (see
Technical
details [
17]
).
}
Make sure that the safety switch and actuator cannot be used as an end stop.
}
Please note the installation measures in accordance with EN ISO 14119 for a safety
switch design 4 and with level of coding High
}
For simpler installation, the mounting brackets (see
Order reference for
Accessories [
21]
) can be used.
}
If using angled connector plugs, note the defined angle of the cable routing.
CAUTION!
Possible loss of the safety function by changing the release distance S
ar
with non-flush installation
Installing the safety switch non-flush within electrically or magnetically con-
ductive material, the value for the assured release distance
S
ar
can change.
– Check the assured release distance
S
ar.