Technical details
Operating Manual PSSu E F 4DI(-T)(-R),
21310-EN-08
33
Operating
Mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
1-channel
PL d
Cat. 2
SIL CL 2
9,10E-09
SIL 2
7,25E-04
20
2-channel
PL e
Cat. 3
SIL CL 3
3,10E-09
SIL 3
1,85E-05
20
2-ch. pulsed
PL e
Cat. 4
SIL CL 3
3,10E-09
SIL 3
1,85E-05
20
1-ch., pulsed
light barrier
PL e
Cat. 4
SIL CL 3
2,91E-09
SIL 3
7,52E-05
20
If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH
D
and PFD will need to be doubled when a safety function is calculated.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are
not
identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.