2
Order Example
PMAC901 –C –0.5S -40
It means the single phase energy meter provides one pulse output, one RS485 COM, class 0.5S accuracy
measurement, maximum rated current is 40A.
4.
Main Technical Parameter
Rated voltage
220VAC
Accuracy
Class 1 or Class 0.5S
Rated current
10(40)A,10(60)A,20(100)A
Dimension 75×88×73mm
Input frequency
50Hz
Installation
mode
Standard 35mm DIN rail
Starting current
0.1%I
n
Operating temperature: -20
℃
~+55
℃
Power supply
220VAC±15%
Storage temperature: -20
℃
~+55
℃
Power consumption <2W
Operating
condition
Relative humidity:
5%~95%,non-condensing
Insulating property
Power frequency withstand voltage: AC 2 KV
Impulse withstand voltage: 6KV
Electrostatic discharge immunity test
IEC61000-4-2, Level 4
Radiated immunity test
IEC61000-4-3, Level 3
Electrical fast transient/ burst immunity test
IEC61000-4-4, Level 3
Surge immunity test
(
1
,
2/50
μ
s~8/20
μ
s
)
IEC61000-4-5, Level 3
Conducted emission
EN55022, Class B
Radiated emission
EN55022, Class B
5. Display and Key-press Operation
5.1 Display Instruction
In energy data displaying interface, the LCD displays KWH value in 6 +1 digits (999999.9 KWh).
In parameter setting interface, the menu setting options are in order of : CT ratio programming, communication
address programming, baud rate programming, clear energy.
5.2 LED Lights Instruction
On the panel of the meter, there are 3 LED lights in order of
(COM), (PULSE), (REV).
(COM)
is communication indicating light. When the communication is normal, the light flashes once every two
seconds. When communication error, the light flashes twice a second. In case communication blackout, the light is
off.