Pilot Communications PMAC901 Installation & Operation Manual Download Page 4

 

2

Order Example 

PMAC901 –C –0.5S -40 
It means the single phase energy meter provides one pulse output, one RS485 COM, class 0.5S accuracy 
measurement, maximum rated current is 40A. 
 

 

4. 

Main Technical Parameter

 

Rated voltage 

220VAC 

Accuracy 

Class 1 or Class 0.5S 

Rated current 

10(40)A,10(60)A,20(100)A 

Dimension  75×88×73mm 

Input frequency 

50Hz 

Installation 

mode 

Standard 35mm DIN rail 

Starting current 

0.1%I

n

 

Operating temperature: -20

~+55

 

Power supply 

220VAC±15% 

Storage temperature: -20

~+55

 

Power consumption  <2W 

Operating 

condition 

Relative humidity: 

5%~95%,non-condensing 

Insulating property 

Power frequency withstand voltage: AC 2 KV 

Impulse withstand voltage: 6KV 

Electrostatic discharge immunity test 

IEC61000-4-2, Level 4 

Radiated immunity test 

IEC61000-4-3, Level 3 

Electrical fast transient/ burst immunity test 

IEC61000-4-4, Level 3 

Surge immunity test

1

2/50

μ

s~8/20

μ

s

 

IEC61000-4-5, Level 3 

Conducted emission 

EN55022, Class B 

Radiated emission 

EN55022, Class B 

 

 

5. Display and Key-press Operation   

 

   

 
5.1 Display Instruction

 

In energy data displaying interface, the LCD displays KWH value in 6 +1 digits (999999.9 KWh). 

In parameter setting interface, the menu setting options are in order of : CT ratio programming, communication 

address programming, baud rate programming, clear energy.   

 

5.2 LED Lights Instruction

 

On the panel of the meter, there are 3 LED lights in order of

 (COM), (PULSE), (REV). 

(COM)

 is communication indicating light. When the communication is normal, the light flashes once every two 

seconds. When communication error, the light flashes twice a second. In case communication blackout, the light is 
off. 

 

Summary of Contents for PMAC901

Page 1: ...PMAC901 Single Phase Energy Meter Installation Operation Manual...

Page 2: ...ameter 2 5 Display and Key press Operation 2 5 1 Display Instruction 2 5 2 LED Lights Instruction 2 5 3 Key press Instruction 3 5 4 Parameter Setting 3 6 Connection Modes and Drawing 5 7 Figure and In...

Page 3: ...of 50Hz or 60Hz three phase alternating current circuit It displays total energy consumption via LCD and is characterized with good reliability compact size light weight specious nice appearance and...

Page 4: ...EC61000 4 2 Level 4 Radiated immunity test IEC61000 4 3 Level 3 Electrical fast transient burst immunity test IEC61000 4 4 Level 3 Surge immunity test 1 2 50 s 8 20 s IEC61000 4 5 Level 3 Conducted em...

Page 5: ...elease to enter programming The screen shows 1 1 1 The last two digits 1 means the current cursor position is on units digit 3 Press several times change the units digit to 0 The screen shows 1 0 1 4...

Page 6: ...twice to enter baud rate menu The screen shows 3 9 6 The number 3 means baud rate setting option The back number 96 means the baud rate is 9600bps The baud rate can be set to 4800bps or 9600bps 2 If...

Page 7: ...rrent 100A the meter should be connected via external CT When rated current 100A the meter should be connected directly 1 PMAC901 direct connection drawing rated current 100A 1 2 3 4 TEST 485 CMbus 5...

Page 8: ...6...

Page 9: ...40005 RO IH Current high 16 bit Current three decimal places Unit A unsigned long 40006 RO PL Active power low 16 bit 40007 RO PH Active power high 16 bit Active power one decimal place Unit W long 4...

Page 10: ...Zhuhai Pilot Electronics Co Ltd Distributor HRW Limited Hong Kong admin hrw hk Tel 852 2546 7402 Fax 852 2546 7403 http www hrw hk...

Reviews: