Pilot Communications PMAC901 Installation & Operation Manual Download Page 3

 

1

1. Product Description 

 

PMAC901 DIN rail energy meter is a kind of new style single phase whole electronic type meter. The meter is 

completely conformed to the relative requirements of the Nation Standard GB/T17215-2008 and International 

Standard IEC 62053:2003 (Class 1 or Class 0.5S). It is an integration of up-to-date micro-electronics technique, 

special imported large scale integrate circuit, advanced technique of digital sampling technique and SMT 

techniques etc.   

 

PMAC901 single phase energy meter is designed for measuring active energy power consumption in a rated 

frequency of 50Hz or 60Hz three phase alternating current circuit. It displays total energy consumption via LCD 

and is characterized with good reliability, compact size, light weight, specious nice appearance and easy 

installation. 

 
 

2. Features 

 

 

35mm DIN installing, in accordance    with Standard DIN ED5002   

 

High accuracy, active energy accuracy up to class 1 or class 0.5S 

 

6+1 digits LCD display 

999999.9 kWh

 

 

Passive pulse output, output signal is in accordance with Standard DIN43864   

 

LED indicates pulse output 

 

Key-press for local parameter setting 

 

RS485 or C-MBUS communication port, Modbus protocol 

 

3. Order Information 

 
 

PMAC901 

- □-  □-  □ 

                   

     

     

     

 

  Communication Port 

One RS485 COM 

One C-MBUS 

  Optional Accuracy  

Active energy class 1 

0.5S 

Active energy class 0.5S 

  Rated Current 

40 

10(40)A 

60 

10(60)A 

100 

20(100)A 

 

Summary of Contents for PMAC901

Page 1: ...PMAC901 Single Phase Energy Meter Installation Operation Manual...

Page 2: ...ameter 2 5 Display and Key press Operation 2 5 1 Display Instruction 2 5 2 LED Lights Instruction 2 5 3 Key press Instruction 3 5 4 Parameter Setting 3 6 Connection Modes and Drawing 5 7 Figure and In...

Page 3: ...of 50Hz or 60Hz three phase alternating current circuit It displays total energy consumption via LCD and is characterized with good reliability compact size light weight specious nice appearance and...

Page 4: ...EC61000 4 2 Level 4 Radiated immunity test IEC61000 4 3 Level 3 Electrical fast transient burst immunity test IEC61000 4 4 Level 3 Surge immunity test 1 2 50 s 8 20 s IEC61000 4 5 Level 3 Conducted em...

Page 5: ...elease to enter programming The screen shows 1 1 1 The last two digits 1 means the current cursor position is on units digit 3 Press several times change the units digit to 0 The screen shows 1 0 1 4...

Page 6: ...twice to enter baud rate menu The screen shows 3 9 6 The number 3 means baud rate setting option The back number 96 means the baud rate is 9600bps The baud rate can be set to 4800bps or 9600bps 2 If...

Page 7: ...rrent 100A the meter should be connected via external CT When rated current 100A the meter should be connected directly 1 PMAC901 direct connection drawing rated current 100A 1 2 3 4 TEST 485 CMbus 5...

Page 8: ...6...

Page 9: ...40005 RO IH Current high 16 bit Current three decimal places Unit A unsigned long 40006 RO PL Active power low 16 bit 40007 RO PH Active power high 16 bit Active power one decimal place Unit W long 4...

Page 10: ...Zhuhai Pilot Electronics Co Ltd Distributor HRW Limited Hong Kong admin hrw hk Tel 852 2546 7402 Fax 852 2546 7403 http www hrw hk...