PIE piecal 334 Operating Instructions Manual Download Page 5

READ V

Choose this function to measure from -99.99 to +99.99V DC.

1) Select  “READ VDC”  with slide switch 

q

.

2)  Connect  the  red  (+)  and  black  (-)  leads  of  the 

PIECAL Model 334 across the voltage source to be 

measured.

Any  DC  voltage  from  -99.99  to  +99.99  volts  may  be 

measured.  Loop  power  supplies,  signal  voltages  at 

receivers, batteries and transmitter voltage drops may 

be  measured.  Signals  exceeding  ±99.99 VDC  will  be 

indicated by OVRLD on the display.

OUT OF RANGE SIGNALS

Signals below 0 mA or open circuits are indicated 

by  0.00  mA  (-25.0%)  on  the  display.  Signals 

above  52  mA  are  current  limited  by  protection 

circuitry to approximately 54 mA.

KEEPING THE PROCESS GOING

When  an  instrument  in  a  critical  control  loop 

develops  a  problem  it  is  important  to  maintain 

control of the process. The PIECAL Model 334 

can  be  substituted  for  a  faulty  controller  or 

transmitter to provide temporary manual control 

of  the  process.  One  technician  takes  manual 

control of the process while a second technician 

retrieves, installs and con gures a replacement 

instrument.

OPEN LOOPS

The  display  will  indicate  0.00  mA  or  -25.0%  if 

there  is  an  open  loop  or  if  the  polarity  is 

reversed. Check all the connections in the loop 

or try reversing the leads.

POWER TRANSMITTER

Adjusting  the  SOURCE  output  to  full  scale 

supplies  a  nominal  24V  DC  to  power  a  2 Wire 

Transmitter  while  simultaneously  displaying  the 

4 to 20 mA output of the transmitter.

READ MILLIAMPS

Select  READ  milliamps  by  moving  slide  switch 

q

 

to “mA”  or “%  4  to  20mA”  and  moving  slide 

switch 

w

  to  “READ”.  Place  the  PIECAL  Model 

334 in the loop in series with the current to be 

measured.

SOURCE MILLIAMPS or 2-WIRE SIMULATOR

Select “SOURCE” using slide switch 

w

 to output 

from 0.00 to 24.00 milliamps using the PIECAL 

Model  334’s  internal  power  source.  This  will 

provide 24V DC.  Select “2-WIRE” to control the 

current  in  loop  that  is  using  an  existing  power 

supply. To change the output current adjust the 

dial knob 

r

. Turning clockwise will increase the 

output  value,  turning  counter-clockwise  will 

decrease  the  output  value.  The  output  is 

adjustable  in  all  EZ-CHECK™  positions. When 

returning  to  the  “4.00mA”/“0.0%”  and 

“20.00mA”/”100%”  positions  they  will  always 

return  to  4.00  (0.0%)  and  20.00  (100.0%)  mA. 

This  method  is  superior  to  keypad  units.  The 

zero  and  full  scale  positions  can  be  adjusted 

smoothly  making  easy  valve  end  stop  testing, 

trip  point  testing,  alarm  testing,  etc.  There  is 

virtually  no  overshoot/undershoot  and  no 

automated modes that need to be learned.

READ DC VOLTS

Select “READ VDC” using slide switch 

q

 to read 

volts DC. Clip the leads across the voltage to be 

measured.

Read DC Volts

Application Notes

Practical Instrument Electronics, Inc.

Available at www.Instrumentation.com 

Summary of Contents for piecal 334

Page 1: ...to check loop response and control settings The PIECAL Model 334 uses any loop power from 2 to 100V DC READ LOOP CURRENT Check controller outputs or measure the milliamp signal anywhere in the loop T...

Page 2: ...displayed in the units selected r DIAL KNOB Turn the knob to adjust output level Turn clockwise to increase the output counter clockwise to decrease the output t EXTERNAL POWER JACK Not Shown When us...

Page 3: ...while the EZ CHECK switch e is in the DIAL position or the current can be set at the xed points of 4 00mA 0 0 or 20 00mA 100 0 with switch e READ mA READ Percent of 4 to 20 mA Choose this function to...

Page 4: ...IECAL Model 334 to the plus input of the device and the black source lead to the minus The PIECAL Model 334 supplies a nominal 24 volts DC at 24 mA to the 2 Wire Transmitter The current passed by the...

Page 5: ...RCE output to full scale supplies a nominal 24V DC to power a 2 Wire Transmitter while simultaneously displaying the 4 to 20 mA output of the transmitter READ MILLIAMPS Select READ milliamps by moving...

Page 6: ...Electronics Inc be liable for any special incidental or consequential damage SETTING UP VALVES When setting up a valve it is important to correctly set the end stops Use the PIECAL Model 334 wo supply...

Page 7: ...dication with nominal 1 hour of operation left Protection against misconnection Over voltage protection to 135 vrms rated for 30 seconds or 240 vrms rated for 15 seconds Display High contrast backlit...

Page 8: ...V at 20 mA Overload Current limit protection 24 mA nominal Loop voltage limits 2 to 100 VDC fuse less protected from reverse polarity connections Battery life 125 hours nominal Voltage Read Range and...