Bolting on the long frame side using four inner-
most mounting holes. Mounting rails run perpen-
dicularly to the long frame side.
Maximum Load:
Uplift load ≤ 2400 Pa
Downforce load ≤ 5400 Pa
Compatible module types : PW60LHT-C,
7.0
MAINTENANCE
•
Do not make modifications to any components
of the PV module (diode, junction box, plug
connectors or others).
•
Regular maintenance is required to keep mo-
dules clear of snow, bird droppings, seeds,
pollen, leaves, branches, dirt spots, and dust.
•
Modules with sufficient tilt (at least 15°), gene-
rally may not require cleaning (rain will have a
selfcleaning effect). If the module has beco-
me soiled, wash with water and a non-abrasive
cleaning implement (sponge) during the cool
part of the day. Do not scrape or rub dry dirt
away, as this may cause micro scratches.
•
Snow should be removed using a soft brush.
•
Periodically inspect the system to check the in-
tegrity of all wiring and supports.
•
To protect against electric shock or injury, elec-
trical or mechanical inspections and mainte-
nance should be performed by qualified per-
sonnel only.
•
Please refer to Annex C (Module Cleaning
Guide) for additional information on this topic.