3.3.18 Diagnostic Mode - Float Switch
This display will communicate to the user the current status
of the Float Switch.
Press the Next button to advance to the next screen.
3.3.19 Diagnostic Mode - Intake RH Offset
The Intake RH Offset allows you to calibrate the DryMAX to
match your favorite meter.
Press the Set button to adjust the intake RH in 1%
increments ranging from -20% to 5. Negative values will
reduce the RH on the display of the DryMAX.
3.3.20 Diagnostic Mode - Fan
Press the Set button to toggle the Fan On/Off.
Press the Next button to advance to the next screen.
3.3.21 Diagnostic Mode - Compressor
Press the Set button to toggle the Compressor On/Off.
Press the Next button to advance to the next screen.
3.3.22 Diagnostic Mode - Display Test
Press the Set button to start the Display test.
3.3.23 Diagnostic Mode - Refrig. Test
The display will communicate to the user the following
information during a Refrigeration Test:
Inlet = Temperature and RH/Grains
Outlet = Temperature and RH/ Grains
Hours = Life hours only.
Evaporator Coil = Temperature
Countdown timer = 20 minutes
Once the 20 minute countdown timer has expired, the
display will automatically advance to show the refrigeration
test results. The display will communicate to the user either
“Refrig. test passed” or “Refrig. test failed”.
Press the Next button to return to the first diagnostic test or
press and hold the Next button for 3 seconds to return to the
Dashboard.
3.4 Condensate Removal
The Phoenix DryMAX is equipped with an internal
condensate pump to remove the water that is condensed
during dehumidification. This allows the condensate
to be pumped up to 6m with the attached hose. If the
condensate must be pumped more than 6m above the unit,
a second pump must be added to relay the condensate. The
condensate pump automatically purges when the reservoir
is full. Use the PURGE
button to manually
remove condensation.